The automation opens and closes at reduced speed. Set the opening and closing times according to the weights and to the door width,
referring to the table:
750
LOW ENERGY
850
1000
1200
The specifi ed times refer to the opening from 00 to 800 and to the closing from 900 to 100.
PUSH&GO
A manual displacement of the leaf from the closed position triggers an automatic opening and closing action
WARNING: each time you change the DIP setting, validate it by performing a RESET of the board, turning it off and then back on.
11.3) "LOW ENERGY" OPERATION
A door operating at "low" energy (not exceeding 1.69 J) shall be set up in such a way as to ensure that:
- The minimum leaf closing times (from 90° to 10°) are equal to or greater than the values listed in Table 1.
- The minimum leaf slow-down time during the closing stage (last 10°) shall be of at least 1.5 s.
- The force required to hold the leaf shall not exceed 67 N anywhere in the closing or opening motion range (applied to the main closing edge in the direction of
travel);
- In the case of power failure or motor failure, the leaf can be released with a force of less than 67N and can be opened with a force of no more than 90N (applied
to the main closing edge in the direction of travel).
Note: a static closing force as high as 150N is allowed anyway when the gap between the main closing edge and the ledge one is ≤8 mm.
Table 1 - Minimum leaf closing times.
Leaf width
(mm)
50
750 mm
3.0 s
850 mm
3.0 s
1,000 mm
3.5 s
1,200 mm
4.0 s
To change the closing speed, please refer to paragraph 12.
12) "DISPLAY" OPERATING PARAMETERS MANAGEMENT
The two 7-segment displays, along with the 4 buttons, allow you to manage all the main parameters and the advanced options, ensuring an optimum management of
the automation for the diff erent installation types.
To properly see the display set the JP2 jumper according to the leaf opening side, referring to the arrows shown in fi gure 17.
The programming procedure is the following:
- Select the parameter to be edited using the [+] or [-] buttons; at this stage the indication on the display is fi xed.
- Press the [ENT] button. The display shows the value currently recorded in the board. This indication is blinking.
- You can change its value using the [+] or [-] buttons – to confi rm the change press the [ENT] button; the display returns to the number associated with the edited parameter.
- Press the [ESC] button to exit the parameter editing mode.
Note: a time-out is activated during the parameter selection/editing stage; if no buttons have been pressed for over 10 seconds the system exits the programming stage.
PARAMETER
DEFINITION
01
Opening speed [°/s]
02
Closing speed [°/s]
03
Normal pause time [s]
Pause time for disabled
04
people [s]
VISTA SW 260 SXL:
Spring closing speed
05
VISTA SW 260 MXL:
Wind resistance with closed
door
Opening Force and Closing
06
Force
07
Acceleration and Deceleration
08
Full closure angle
09
Electric lock voltage
10
Electric lock type
Electric pulse management time
11
Opening delay after lock release
12
Electric lock closing force
INSTALLATION MANUAL
Leaf weight (kg)
50
60
70
80
90
3,0s
3,0s
3,0s
3,0s
3,5s
3,0s
3,0s
3,5s
3,5s
4,0s
3,5s
3,5s
4,0s
4,0s
4,5s
4,0s
4,5s
4,5s
5,0s
5,5s
Leaf weight (kg)
60
70
80
3.0 s
3.0 s
3.0 s
3.0 s
3.5 s
3.5 s
3.5 s
4.0 s
4.0 s
4.5 s
4.5 s
5.0 s
MIN
MAX
DEFAULT
20
70
60
10
40
20
0
60
0
5
60
5
1
9
5
0
9
0
1
9
5
5
30
30
10
40
20
0
1
0
0
6
0
0
9
2
0
9
5
90
3.5 s
4.0 s
4.5 s
5.5 s
PERSONAL
 
Motor speed during the opening stage (adjustment step 5°/s).
 
Motor speed during the closing stage (adjustment step 5°/s).
Waiting time before automatic closing.
62: 2 min
 
63: 3 min
64: 4 min
Waiting time before automatic closing when the disabled people opening command is used or
in Low Energy mode (adjustment step 1s).
 
62: 2 min
63: 3 min
64: 4 min
 
Spring closing speed (1=minimum speed, 9=maximum speed).
It adjusts the wind resistance force with closed door
 
(0=wind resistance force disabled, 1=wind resistance force enables at minimum level, 9=wind
resistance force enabled at maximum level).
Force exerted by the leaf during the opening and closing stage before an obstacle alarm is
 
generated. (1=more sensitive; 9=less sensitive).
 
Acceleration and deceleration speed (adjustment step 1).
 
It adjusts the full closure angle (closing is 1/2 of opening).
0 = 12V electric lock output
 
1 = 24V electric lock output
0= not used
 
For information about the type of electric locks that can be used please refer to the paragraph
"ELECTRIC LOCK MANAGEMENT".
The time depends on the electric lock type:
 
see the "ELECTRIC LOCK MANAGEMENT" paragraph.
 
Force exerted by the leaf to allow the lock coupling.
DESCRIPTION
VISTA SW 260 SXL / VISTA SW 260 MXL -