p4108[0...5] = 1
Measuring
X53x.1
method
A
X53x.2
0: 1x2-conductor
1: 2x2-conductor
D
2: 3-conductor
3: 4-conductor
Cable R meas
Determine cable resistance
p4109[6...11]
(with short-circuited sensor)
x = 1, 2,
3, 4, 5, 6
p4119[6...11]
Measuring
50/60 Hz
method
A
0: 1x2-conductor
X53x.3
1: 2x2-conductor
D
X53x.4
2: 3-conductor
3: 4-conductor
[9625]
Temperature evaluation
p4121 (0)
Channel 6
Filt f_line
...
Channel 11
<1> For p4102[0...23] = 251 °C the evaluation of the appropriate threshold is deactivated.
<2> p4100[0...11]
= 0: Evaluation deactivated
= 1: PTC thermistor (with monitoring for short-circuit)
= 2: KTY84 (with monitoring for wire break and short-circuit)
= 4: Bimetal NC contact (no monitoring)
= 5: PT100 (with monitoring for wire break and short-circuit)
= 6: PT1000 (with monitoring for wire break and short-circuit)
<3> For p4103 = 0 s and sensor type "KTY84", "PT100", "PT1000" (p4100[0...11] = 2, 5, 6) the following applies:
- The relevant fault can only be triggered via the fault threshold (the timer output is always logical 0).
For p4103 = 0 s and sensor type "PTC thermistor", "Bimetal NC contact" (p4100[0...11] = 1, 4) the following applies:
- The corresponding alarm and fault are output simultaneously (delay time = 0 s).
1
2
DO: TM150
Terminal Module 150 (TM150) - Temperature evaluation 2x2-conductor (Channel 0 ... 11)
Temperature evaluation
Channel 0
...
Channel 5
Save cable
Cable R value
resistance
p4110[6...11]
250 °C
R
PT1000
Calculate
resistance
+
T
-99 °C
250 °C
R
PT100
0
1
T
-99 °C
250 °C
R
Temp filt T
KTY84
r4120
T
-99 °C
PTC/
Bimetal
NC
1
contact
0
Sensor R
250 °C
r4101[6...11]
1650 Ÿ (PTC)
100 Ÿ (Bimetal)
3
4
[9626]
Alarm threshold
-99...251 [°C]
p4102[12, 14, 16, 18, 20, 22] (251)
<1>
1
Sensor type
p4100[6...11]
0
<2>
PT1000
6
p4118[6...11] (5)
PT100
5
Bimetal
4
Fault threshold
-99...251 [°C]
KTY84
2
p4102[13, 15, 17, 19, 21, 23] (251)
PTC
1
0
-300 °C
1
0
-50 °C
Temperature actual value
Alarm is present
-300 °C
5
6
fp_9627_51_eng.vsd
15.11.11 V04.05.00
26000.00 μs
"Channel y alarm is present"
0.0...600.0 [s]
r4104.12
A35412 (Channel 6)
p4103[6...11] (0.0)
r4104.14
A35413 (Channel 7)
<3>
r4104.16
A35414 (Channel 8)
T
0
r4104.18
A35415 (Channel 9)
r4104.20
A35416 (Channel 10)
r4104.22
A35417 (Channel 11)
"Channel y fault is present"
1
r4104.13
F35402 (Channel 6)
r4104.15
F35403 (Channel 7)
<1>
r4104.17
F35404 (Channel 8)
1
r4104.19
F35405 (Channel 9)
r4104.21
F35406 (Channel 10)
only for
0
KTY84, PT100,
r4104.23
F35407 (Channel 11)
PT1000
A35926 ... A35931
"Error temperature sensor channel y"
(y = 6 ... 11)
0
Temp act value
r4105[6...11]
1
Group formation
7
8
Function diagram
- 9627 -
SINAMICS