P47 = "Loop break alarm" function.
P47 =
P47 =
P47 =
P47 =
"Loop break alarm" function.
"Loop break alarm" function.
"Loop break alarm" function.
"Loop break alarm" function.
dIS =
Alarm not used
Enb =
The alarm condition of the "Loop break alarm" (LBA)
will be shown by the OUT 3 LED only.
EnbO = The alarm condition of the "Loop break alarm" (LBA)
will be shown by the OUT 3 LED and by the OUT 3
relay status.
N O T E S :
N O T E S :
N O T E S :
N O T E S :
N O T E S :
1) The alarm 2, the Output 1 failure detection and the loop
break alarm are in OR condition on the same output
(OUT 3).
2) The loop break alarm reset type is programmed by P13
parameter.
3) For more details see "Loop Break Alarm function" at
pag 18.
P48 =
P48 =
P48 =
P48 =
P48 =
"Loop break alarm" deviation.
"Loop break alarm" deviation.
"Loop break alarm" deviation.
"Loop break alarm" deviation.
"Loop break alarm" deviation.
This parameter is available only when P47 is different
from dIS.
Programmable from 0 to 500 units
P49 =
P49 =
P49 =
P49 =
P49 =
"Loop break alarm" time.
"Loop break alarm" time.
"Loop break alarm" time.
"Loop break alarm" time.
"Loop break alarm" time.
This parameter is available only when P47 is different
from dIS.
Programmable from 00.01 to 40.00 mm.ss.
P50 = "Loop break alarm" hysteresis.
P50 = "Loop break alarm" hysteresis.
P50 = "Loop break alarm" hysteresis.
P50 = "Loop break alarm" hysteresis.
P50 = "Loop break alarm" hysteresis.
This parameter is available only when P47 is different
from dIS.
Programmable from 1to 50% of the power output.
P51 =
P51 =
P51 =
P51 =
P51 =
Security code for configuration parameters
Security code for configuration parameters
Security code for configuration parameters
Security code for configuration parameters
Security code for configuration parameters
0
No protection (it is always possible to modify all
configuration parameters);
1
always protected (it is not possible to modify any
configuration parameter);
from 2 to 9999 security code for configuration parameter
protection.
Notes:
Notes:
Notes:
Notes:
Notes:
1) If a value from 2 to 9999 has been assigned as security
code it cannot be displayed anymore, when returning on
this parameter the display will show "On".
XKS-1-B0.pmd
15
2) If the security code is forgotten a new value can be set.
3) For configuration parameter only is available a passe-
partout code, by this code it is possible to enter in
modify configuration mode even if the configuration
parameters are protected (S.CnF = 1 or from 2 to
9999).
The passe-partout code is located in Appendix A.
4) Fill out and cut the part of the Appendix A reserved to
the security codes if it is desired to keep them secrets.
C. End = End configuration
C. End = End configuration
C. End = End configuration
C. End = End configuration
C. End = End configuration
This parameter allows to come back to the run time mode.
NO =
the instrument remains in configuration mode and
comes back to the first display of the configura-
tion mode (dF.Cn).
YES = This selection ends the configuration mode. the
instrument performs an automatic reset and restart
the run time mode.
GB
GB
GB
GB
GB
15