14 = mA
Linear
range
4 /
15 = V
Linear
range
0 /
16 = V
Linear
range
1 /
17 = V
Linear
range
0 /
18 = V
Linear
range
2 /
19 = TC type
L
range
0 /
20 = TC type
J
range
-150 /
21 = TC type
K
range
-150 /
22 = TC type
N
range
-150 /
23 = TC type
R
range
0 /
24 = TC type
S
range
0 /
25 = RTD type
Pt 100
range
-199.9 /
26 = RTD type
Pt 100
range
-330 /
27 = TC type
T
range
-199.9 /
28 = TC type
T
range
-330 /
NOTE: selecting P1 = 0, 2, 4, 9, 25 or 27, the instrument set
NOTE
NOTE
NOTE
NOTE
automatically P40 = FLtr. For all the remaining ranges it will set
P40 = nOFL.
P2 = Decimal point position
P2 = Decimal point position
P2 = Decimal point position
P2 = Decimal point position
P2 = Decimal point position
This parameter is available only when a linear input is selected
(P1 = 11 to 18).
----.
= No decimal figure.
---.-
= One decimal figure.
--.--
= Two decimal figures.
-.---
= Three decimal figures.
P3 = Initial scale value
P3 = Initial scale value
P3 = Initial scale value
P3 = Initial scale value
P3 = Initial scale value
For linear inputs it is programmable from -1999 to 4000.
For TC and RTD input it is programmable within the input
range.
Notes:
Notes:
Notes:
Notes:
Notes:
1) When this parameter is modified, rL parameter will be
re-aligned to it.
2) If a linear input is selected, the value of this parameter
can be greater than P4 in order to get a reverse
readout.
P4 = Full scale value
P4 = Full scale value
P4 = Full scale value
P4 = Full scale value
P4 = Full scale value
For linear inputs it is programmable from -1999 to 4000.
For TC and RTD inputs, it is programmable within the
input range.
XKS-1-B0.pmd
10
20 mA
N o t e s :
N o t e s :
N o t e s :
N o t e s :
N o t e s :
5 V
1) When this parameter is modified, rH parameter will be re-
5 V
aligned to it.
10 V
2) If a linear input is selected, the value of this parameter can
be smaller than P3 in order to get a reverse readout.
10 V
+1650 °F
The initial and full scale values determine the input span which
+1830 °F
is used by the PID algorithm, the SMART and the alarm
functions.
+2500 °F
+2550 °F
NOTE
NOTE: the minimum input span (S = P4 - P3), in absolute
NOTE
NOTE
NOTE
+3200 °F
+3200 °F
value, should be set as follows:
+400.0 °F
- For linear inputs, S > 100 units.
- For TC input with °C readout, S > 300 °C.
+1470 °F
- For TC input with °F readout, S > 550 °F.
400.0 °C
- For RTD input with °C readout, S > 100 °C.
750 °F
- For RTD input with °F readout, S > 200 °F.
P5 = Output 1 type
P5 = Output 1 type
P5 = Output 1 type
P5 = Output 1 type
P5 = Output 1 type
Changing the P5 setting, also Cy1 parameter will be
automatically modified.
rEL = Relay [the cycle time (Cy1) will be forced to
SSr = SSR [the cycle time (Cy1) will be forced to 4 s]
P6 = Output 1 action
P6 = Output 1 action
P6 = Output 1 action
P6 = Output 1 action
P6 = Output 1 action
This parameter is skipped if P7 = 4
rEV = Reverse action (Heating action)
dir = Direct action (Cooling action)
Reverse
INPUT
INPUT
t
OUTPUT
OUTPUT
t
GB
GB
GB
GB
GB
10
20/06/2005, 11.09
15 s]
Direct
t