ero electronic TKS Manuel De Service page 8

Masquer les pouces Voir aussi pour TKS:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
RTD INPUT
RTD
RTD
4
3
1
4
3
1
Fig. 3
RTD INPUT WIRING
Input: for RTD Pt 100 Ω, 3-wire connection.
Input
Input
Input
Input
Line resistance
Line resistance
Line resistance
Line resistance
Line resistance: automatic compensation up to 20 Ω/wire
with no measurable error.
NOTES:
NOTES
NOTES
NOTES
NOTES
1 ) Don't run input wires together with power cables.
2 ) Pay attention to the line resistance; a high line
resistance may cause measurement errors.
3 ) When shielded cable is used, it should be grounded at
one side only to avoid ground loop currents.
4 ) The resistance of the 3 wires must be the same.
XKS-1-B0.pmd
2
LINEAR INPUT
LINEAR INPUT
LINEAR INPUT
LINEAR INPUT
LINEAR INPUT
1
3
1
3
Fig. 4
mA, mV AND V INPUTS WIRING
NOTES
NOTES
NOTES
NOTES
NOTES:
1) Don't run input wires together with power cables.
2) Pay attention to the line resistance; a high line
resistance may cause measurement errors.
3 ) When shielded cable is used, it should be grounded at
one side only to avoid ground loop currents.
Input type
Input type
Input type
Input type
Input type
impedance
impedance
impedance
impedance
impedance
11
0 - 60 mV
0 - 60 mV
0 - 60 mV
0 - 60 mV
0 - 60 mV
> 1 MΩ
12
12 - 60 mV
12 - 60 mV
12 - 60 mV
12 - 60 mV
12 - 60 mV
13
0 - 20 mA
0 - 20 mA
0 - 20 mA
0 - 20 mA
0 - 20 mA
< 5 Ω
14
4 - 20 mA
4 - 20 mA
4 - 20 mA
4 - 20 mA
4 - 20 mA
15
0 - 5 V
0 - 5 V
0 - 5 V
0 - 5 V
0 - 5 V
> 200 kΩ
16
1 - 5 V
1 - 5 V
1 - 5 V
1 - 5 V
1 - 5 V
17
0 - 10 V
0 - 10 V
0 - 10 V
0 - 10 V
0 - 10 V
> 400 kΩ
18
2 - 10 V
2 - 10 V
2 - 10 V
2 - 10 V
2 - 10 V
GB
GB
GB
GB
GB
2
20/06/2005, 11.08
+
mA,
mV
or
_
V
Shield
+
mA,
_
mV
or
V
G
Accuracy
Accuracy
Accuracy
Accuracy
Accuracy
0.2 % + 1 digit
@ 25°C