B) LOGIC INPUT
B) LOGIC INPUT
B) LOGIC INPUT
B) LOGIC INPUT
B) LOGIC INPUT
SP / SP2
8
7
Fig. 5 - LOGIC INPUT WIRING
This logic input allows to select the operative set point.
logic input
op. set point
open
SP
close
SP2
Safety notes:
Safety notes:
Safety notes:
Safety notes:
Safety notes:
1 ) Do not run logic input wiring together with power
cables.
2 ) Use an external dry contact capable of switching 0.5
mA, 5 V DC.
3 ) The instrument needs 100 ms to recognize a contact
status variation.
4 ) The logic input is NOT
NOT isolated by the measuring input
NOT
NOT
NOT
XKS-1-B0.pmd
3
CURRENT TRANSFORMER INPUT
CURRENT TRANSFORMER INPUT
CURRENT TRANSFORMER INPUT
CURRENT TRANSFORMER INPUT
CURRENT TRANSFORMER INPUT
This input allows to measure and display the current
running through the load, driven by the OUTPUT 1, during
the ON and the OFF period of the OUT 1 cycle time.
By this features it is also available the "Out 1 failure
detection" function (see page 18)
5
6
Current
transformer
Load
Fig. 6
CURRENT TRANSFORMER INPUT
WIRING
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
1 ) The input impedance is equal to 10 Ω.
2 ) The maximum input current is equal to 50 mA (50 / 60
Hz).
3 ) The minimum period (ON or OFF) to perform this
measurement is equal to 400 ms.
Scaling: programmable from 10 A to 100 A (with 1A step).
Scaling
Scaling
Scaling
Scaling
Resolution
Resolution
Resolution
Resolution:
Resolution
- for full scale up to 20 A: 0.1 A.
- for full scale from 21 A to 100 A: 1 A
Safety note:
Safety note:
Safety note:
Safety note:
Safety note:
- Do not run current transformer input wiring together
with power cables.
GB
GB
GB
GB
GB
3
20/06/2005, 11.08