Default Parameters - ero electronic TKS Manuel De Service

Masquer les pouces Voir aussi pour TKS:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

APPENDIX A
APPENDIX A
APPENDIX A
APPENDIX A
APPENDIX A

DEFAULT PARAMETERS

DEFAULT PARAMETERS
DEFAULT PARAMETERS
DEFAULT PARAMETERS
DEFAULT PARAMETERS
DEFAULT RUN TIME PARAMETERS
DEFAULT RUN TIME PARAMETERS
DEFAULT RUN TIME PARAMETERS
DEFAULT RUN TIME PARAMETERS
DEFAULT RUN TIME PARAMETERS
PARAMETER
PARAMETER
PARAMETER
PARAMETER
PARAMETER
DEFAULT VALUE
DEFAULT VALUE
DEFAULT VALUE
DEFAULT VALUE
DEFAULT VALUE
SP
= Initial scale value
SnRT
= Disable
n.SRt
= OFF
SP2
= Initial scale value
nnn
= OFF
AL1
= Initial scale value for process alarm
0 for deviation or band alarm
HSA1
= 0.1 %
AL2
= Initial scale value for process alarm
0 for deviation or band alarm
HSA2
= 0.1 %
AL3
= Initial scale value for process alarm
= 0 for deviation or band alarm
HSA3
= 0.1 %
PB
= 4.0 %
HyS
= 0.5 %
ti
= 4.00 (4 minutes)
td
= 1.00 (1 minute)
XKS-A-B0.pmd
1
IP
= 30 % if one control output is
configured
= 0 if two control outputs are
configured
Cy1
= 15 seconds for relay output
= 4 seconds for SSR output
Cy2
= 10 seconds for P8 = AIr
= 4 seconds for P8 = OIL
= 2 seconds for P8 = H2O
rC
= 1.00 for P8 = AIr
= 0.80 for P8 = OIL
= 0.40 for P8 = H2O
OLAP
= 0
rL
= Initial scale value
rH
= Full scale value
Grd 1
= Infinite (step transfer)
Grd 2
= Infinite (step transfer)
OLH
= 100 %
tOL
= Infinite
Hbd
= 50 % of the full scale value
SCA
= 100% of the full scale value
rnP
= Infinite
Appendix A.1
20/06/2005, 10.55

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Mks