Procedure With An Empty Signal (Connexx Switch) - Ecolab CONNEXX Basic Manuel Technique

Appareil pourvu de signal vide pour le prélèvement et la purge automatiques des produits qui dégagent du gaz à partir de réservoirs avec lance d'aspiration intégrée
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6.2

Procedure with an empty signal (Connexx Switch)

Empty signal for container 1 with switchover to container 2 and subsequent empty signal for
container 2
Status / action
Containers 1 and 2 full
Container 1 active
Level switch at the top
Pump operates
Container 1 empty
Level switch at the bottom
Injector solenoid valve opens -> suction starts
Pump Enable cancelled -> pump stops
Valve 1 closes, injector solenoid valve closes
Valve 2 opens, container 2 active
Injector solenoid valve opens -> suction starts
Level switch at the top
Container 1 is changed
Switch off alarm (buzzer) with the Quit button
Replace container 1
Acknowledge empty signal with button LL1
The control unit is now ready to switch from container 1 after the empty signal for container 2
Container 1 is not changed
Container 2 empty
Level switch at the bottom
Injector solenoid valve opens -> suction starts
Pump enable cancelled -> pump stops
Valve 1 closes, injector solenoid valve closes
No automatic switchover to container 2 due to
active empty signal LL1
Switch off alarm (buzzer) with the Quit button
Replace container 1
Acknowledge empty signal with button LL1
Injector solenoid valve opens -> suction starts
Replace container 2
Acknowledge empty signal with button LL2
Level switch at the top
417101375_Connexx.doc
LED
Control unit
LL1 lights up green
LL2 off
Quit off
Pump Enable active
Pump Enable timer starts (5 secs.)
Empty signal timer starts (X secs.)
Pump Enable timer expired
Empty signal timer expired
LL1 flashes red (empty)
LL2 flashes green (active)
Quit off
Empty signal timer starts (X secs.)
Pump Enable active
LL1 off
Quit off
Alarm (buzzer) off
Pump Enable timer starts (5 secs.)
Empty signal timer starts (X secs.)
Pump Enable timer expired
Empty signal timer expired
LL1 flashes red
LL2 lights up green
Quit lights up red (collective alarm signal)
Alarm (buzzer) active
Empty signal timer starts (X secs.)
LL1 flashes green (active)
LL2 off (standby)
Quit off
Pump Enable active
- 51 -
Rev. 11-02.10