Procedure With An Empty Signal (Connexx Basic); Control Unit - Ecolab CONNEXX Basic Manuel Technique

Appareil pourvu de signal vide pour le prélèvement et la purge automatiques des produits qui dégagent du gaz à partir de réservoirs avec lance d'aspiration intégrée
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5. Adjust the output time
The output time should be adjusted as a function of the time to fill the lifting vessel (3
filling procedures = 30 seconds) (see chapter 4.4.2).
6. Check all the unions on the equipment for leaks. Check the exhaust air hose.
8. Drain the lifting vessel filled with water.
Connexx Basic:
- Switch off the main switch
- Unscrew the throttle screw
- The vessel will drain automatically into the container through the suction line
Connexx Switch:
- Switch off the main switch
- Bridge the level switch contacts (X1, terminals 18 and 19) so that suction
cannot be started
- Unscrew and remove the throttle screw for venting
- Switch on the main switch to activate the compressed air for opening the diaphragm
valve
In order to activate the non-active container, the appropriate button LL1 or LL2 must be
NOTE
pressed when switching on.
- Unscrew and remove the throttle screw for venting
The vessel will drain automatically into the active container through the suction line
6.1

Procedure with an empty signal (Connexx Basic)

Status / action
Container 1 full
Level switch at the top
Pump operates
Container 1 empty
Level switch at the bottom
Injector solenoid valve opens -> suction starts
Pump enable cancelled -> pump stops
Injector solenoid valve closes
Switch off alarm (buzzer) with the Quit button
Replace container 1
Acknowledge empty signal with button LL1
Injector solenoid valve opens -> suction starts
Level switch at the top
417101375_Connexx.doc
LED

Control unit

LL1 lights up green
Quit off
Pump Enable active
Pump Enable timer starts (5 secs.)
Empty signal timer starts (X secs.)
Pump Enable timer expired
Empty signal timer expired
LL1 flashes red
Quit lights up red (collective alarm signal)
Alarm (buzzer) active
LL1 lights up green
Quit off
Empty signal timer starts (X secs.)
Pump Enable active
- 50 -
Rev. 11-02.10