Description
The menu with inputs for the running time of the
system in specific volume flow ranges
Running time in volume flow range from under
9.9 % / 10 – 19.9 % / 20 – 29.9 % / 30 – 39.9 % /
40 – 49.9 % / 50 – 59.9 % / 60 – 69.9 % / 70 –
79.9 % / 80 – 89.9 % / over 90 % of volume flow
value in 4.4.1.1.
The running time is only updated if at least one
pump is running.
The system-specific 100 % value of the volume
flow for the histogram in 4.4.0.1 – 4.4.1.0
Settings
Communication settings
Modbus
Baud rate
The slave address of this switchgear.
The Modbus connection can be deactivated by
selecting the slave address 0.
Parameter range
Factory setting
9.6
19.2
38.4
76.8
0 ... 10 ... 247