10 Faults, causes and remedies

Have faults remedied by qualified personnel
only! Observe the safety instructions in the
Safety chapter.

10.1 Fault display and acknowledgement

If a fault occurs, the red fault signal LED lights up,
the collective fault signal is activated and
Fig. 11: Fault acknowledgement sequence

10.2 History memory for the faults

A history memory has been set up for the switch -
gear and operates according to the FIFO principle
(first in, first out). The memory is configured for
16 faults.
The fault memory can be retrieved using menus
6.1.0.1 – 6.1.1.6.
Code
E040
E040.2
E043
E054
E060*
E061*
E062
Installation and operating instructions Wilo-Control SC-Booster (SC, SC-FC, SCe)
Fault description
Output pressure sensor
faulty
Supply pressure sensor faulty
External setpoint faulty
Connection partner lost
Maximum pressure exceeded The output pressure of the
Pressure below minimum
value
Low water
the fault is displayed on the LCD (error code
number).
A faulty pump is indicated on the main screen by a
flashing status symbol for the corresponding
pump.
The fault can be acknowledged in menu 6.1.0.0
by the following operation:
Causes
Pressure sensor defective
No electrical connection to the
sensor
No electrical connection to the
remote station
Fault in the CAN connection
between the switchgear and
pumps
system has risen above the value
set in menu 5.4.1.0 (e.g. due to a
controller fault)
The output pressure of the
system has dropped below the
value set in menu 5.4.2.0
(e.g. due to a pipe burst)
Protection against low water level
triggered
English
Remedies
Replace sensor
Repair the electrical
connection
Repair the electrical
connection
Check cable connection
Check activation of the
terminating resistors
Check controller function
Check installation
Check whether the default
value corresponds to local
conditions
Check pipe and repair if
necessary
Check inlet/break tank; pumps
restart automatically