Assa Abloy OneSystem 819N Notice De Montage page 51

Serrure multipoints électrique
Masquer les pouces Voir aussi pour OneSystem 819N:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Tab. 2 :
Classification key in
accordance
with EN 179
www.assaabloy.de
Service /Downloads /
Leistungserklärungen
Notices
EN 179 emergency exit door locks
The properties of locks are described by the ten-digit classification key according to
EN 179.
Tab. 2 explains the classification key.
Class
Meaning
3
High usage frequency in situations when there is little incentive to be careful, thus pos-
ing the possibility of accidents or misuse.
7
200,000 test cycles
7
Door mass greater than 200 kg (300 kg)
B
Suitable for use on fire and smoke protection doors on the basis of testing in accord-
ance with EN 1634-1
1
Suitable for critical security function
3
High corrosion resistance in accordance with EN 1670:2007 Section 5.6
2
Intrusion protection up to 1,000 N
2
Up to 100 mm projection (normal projection) of the operating element
A
Emergency exit lock with handle actuation
B/D
For installation in
· B
· single-leaf doors (lock without unlocking pin)
· D
· single-leaf doors opening inwards only (lock without unlocking pin)
CE marking
C
0432–CPR–00007–14
EN 179:2008
ASSA ABLOY
Sicherheitstechnik GmbH
Bildstockstraße 20
72458 Albstadt
GERMANY
2016
3
7
7
B
1
3
2
B
2
A
D
EN
51