Warnings!
General markings:
l
Use 60/75 °C or 75 °C copper wire only.
Maximum ambient temperature 55 °C, with reduced output current.
l
Markings provided for the supply units:
Suitable for use on a circuit capable of delivering not more than 5000 rms
l
symmetrical amperes, 480 V max, when protected by K5 or H Fuses (400/480 V
devices).
Alternate - Circuit breakers (either inverse-time or instantaneous trip types) may
l
be used in lieu of above fuses when it is shown that the let-through energy (i
and peak let-through current (I
will be less than that of the non-semiconductor type K5 fuses with which the drive
has been tested.
Alternate - An inverse-time circuit breaker may be used, sized upon the input
l
rating of the drive, multiplied by 300 % .
Markings provided for the inverter units:
The inverter units shall be used with supply units which are provided with
l
overvoltage devices or systems in accordance with UL840 2nd ed., Table 5.1.
The devices are provided with integral overload and integral thermal protection for
l
the motor.
The devices are not provided with overspeed protection.
l
Terminal tightening torque of lb-in (Nm)
X 21, X 22, X 23, X 24
l
– 10,6 ... 13,3 lb-in (1,2 ... 1,5 Nm)
X4, X6, X14
l
– 1,95 ... 2,2 lb-in (0,22 ... 0,25 Nm)
X 25
l
– 4,4 ... 7,1 lb-in (0,5 ... 0,8 Nm)
Wiring diagram AWG
X 21, X 22, X 23, X 24
l
– AWG 12 ... AWG 8
X4, X6, X14
l
– AWG 28 ... AWG 16
X 25
l
– AWG 24 ... AWG 12
Consignes de sécurité