Technical Specifications; General; Electrical Specifications - Rotex RDLQ011AA6V3 Mode D'emploi

Masquer les pouces Voir aussi pour RDLQ011AA6V3:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 111
T
ECHNICAL SPECIFICATIONS

General

Nominal capacity
• cooling
• heating
Dimensions H x W x D
Weight
• machine weight
• operation weight
Connections
• water inlet/outlet
• water drain
• refrigerant liquid side
• refrigerant gas side
Expansion vessel
• volume
• maximum working pressure (MWP)
Pump
• type
• no. of speed
(b)
Sound pressure level
• heating
• cooling
Internal water volume
Pressure relief valve water circuit
Operation range - water side
• heating
• cooling
Operation range - air side
• heating
• cooling
• domestic hot water by heat pump
(a) FBSP = Female British Standard Pipe
(b) At 1 m in front of the unit (free field condition)
(c) Models can reach –25°C, but this is without capacity guarantee
Electrical specifications
Standard unit (power supply via unit)
• power supply
• nominal running current
Backup heater
• power supply
• maximum running current
Installation manual
33
V3 models (1~)
RD_011
RD_014
RD_016
RB_011
Refer to the Technical Data
Refer to the Technical Data
1418 x 1435 x 382
180 kg
185 kg
(a)
G 5/4" FBSP
hose nipple
Ø9.5 mm (3/8 inch)
Ø15.9 mm (5/8 inch)
10 l
3 bar
water cooled
2
51 dBA
51 dBA
52 dBA
51 dBA
50 dBA
5.5 l
3 bar
+15~+55°C
–20~+35°C
–20~+35°C
V3 models (1~)
230 V 50 Hz 1P
See "Connection of the backup heater power supply" on page 15
See "Connection of the backup heater power supply" on page 15
RB_014
RB_016
RD_011
RD_014
51 dBA
52 dBA
49 dBA
51 dBA
52 dBA
54 dBA
+15~+55°C
+15~+55°C
+5~+22°C
–20~+35°C
–20~+35°C
+10~+46°C
–20~+35°C
–20~+35°C
W1 models (3N~)
RD_016
RB_011
RB_014
RB_016
Refer to the Technical Data
Refer to the Technical Data
1418 x 1435 x 382
180 kg
185 kg
(a)
G 5/4" FBSP
hose nipple
Ø9.5 mm (3/8 inch)
Ø15.9 mm (5/8 inch)
10 l
3 bar
water cooled
2
53 dBA
49 dBA
51 dBA
53 dBA
50 dBA
52 dBA
54 dBA
5.5 l
3 bar
+15~+55°C
+5~+22°C
(c)
(c)
–20~+35°C
+10~+46°C
(c)
(c)
–20~+35°C
W1 models (3N~)
400 V 50 Hz 3P
5.8 A
R(D/B)LQ011~016AA6V3+W1
Unit for air to water heat pump system
4PW53149-1

Publicité

Table des Matières
loading

Table des Matières