UP AND CONFIGURATION
The unit should be configured by the installer to match the installation
environment (outdoor climate, installed options, etc.) and user
expertise.
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.

DIP switch settings overview

DIP switch SS2 is located on the switch box PCB (see "Switch box
main components (door 2)" on page 9) and allows configuration of
domestic hot water tank installation, room thermostat connection and
pump operation.
Switch off the power supply before opening the switch box
service panel and making any changes to the DIP switch
settings.
DIP
switch
SS2
Description
1
Not applicable for installer
2
Domestic hot water tank
installation
(see "Domestic hot water
tank installation
configuration" on page 20)
3
Room thermostat
connection
(see "Room thermostat
installation configuration"
on page 19)
(a)
4
This setting
decides the
operation mode when
there is a simultaneous
demand for more space
heating/cooling and
domestic water heating.
(a) only applicable in case DIP switch 2 = ON
Room thermostat installation configuration
When no room thermostat is connected to
the unit, toggle switch SS2-3 should be set to
OFF.
When a room thermostat is connected to the
unit, toggle switch SS2-3 should be set to ON.
On the room thermostat, set the hysteresis appropriately to
prevent the pump from repeatedly turning on and off (i.e.
chattering), and thereby impacting the lifetime of the pump.
NOTE
When a room thermostat is connected to the unit,
the heating and cooling schedule timers are never
available. Other schedule timers are not affected.
For more information on the schedule timers, refer
to the operation manual.
When a room thermostat is connected to the unit,
and the = button or y button is pressed, the
centralised control indicator e will flash to
indicate that the room thermostat has priority and
controls on/off operation and change over
operation.
Installation manual
19
1
2
3
4
ON
OFF
(Default)
Installed
Not installed
(Default)
Room thermostat
No room
connected
thermostat
connected
(Default)
Heating/cooling
No priority
priority
(Default)
1
2
3
1
2
3
The following table summarizes the required configuration and
thermostat wiring at the terminal block in the switch box. Pump
operation is listed in the third column. The three last columns indicate
whether the following functionality is available on the user interface
(UI) or handled by the thermostat (T):
space heating or cooling on/off (y)
heating/cooling changeover (=)
heating and cooling schedule timers (pr)
Thermostat
Configuration
No thermostat
• SS2-3 = OFF
• wiring: (non)
H C L N
1 2 3 4
• SS2-3 = ON
• wiring:
H C L N
1 2 3 4
Heating only
• SS2-3 = ON
thermostat
• wiring:
H C
1 2 3 4
th
Thermostat with
• SS2-3 = ON
heating/cooling
• wiring:
switch
H C
1 2 3 4
H
th
(a) The pump will stop when space heating/cooling is turned off or when the water
4
reaches the desired water temperature as set on the user interface. With space
heating/cooling turned on, the pump will then run every 5 minutes during 3
minutes to check the water temperature.
Pump operation configuration
4
NOTE
To set the pump speed, refer to "Setting the pump
speed" on page 20.
Without room thermostat
When no thermostat is connected to the unit, pump operation will be
determined by the leaving water temperature.
To force continuous pump operation when no room thermostat is
connected do the following:
-
set toggle switch SS2-3 to ON,
-
short-circuit the terminal numbers 1-2-4 on the terminal block
in the switch box.
With room thermostat
When a thermostat is connected to the unit, the pump will operate
continuously whenever there is heating or cooling demand requested
by the thermostat.
Pump
y
y
y
y
operation
determined by
UI
leaving water
(a)
temperature
X2M
on when space
UI
heating or
cooling is on
X2M
(y)
on when
T
heating
request by
X2M
room
thermostat
L N
on when
T
heating
request or
X2M
cooling request
by room
L N
thermostat
C
th =
Thermostat contact
C =
Cooling contact
Heating contact
H =
L, N =
230 V AC
R(D/B)LQ011~016AA6V3+W1
Unit for air to water heat pump system
=
=
=
=
p p p p r r r r
UI
UI
UI
UI
T
4PW53149-1