097 Performing the walk test
If the walk test is activated, you can trigger all zones of the
alarm centre to check their function. Activate the walk test and
then trigger all zones in sequence. You should also test the
tamper contact. Proceed as follows:
1. On the control unit, enter:
2. The LCD display shows: 097: Walk Test
3. Trigger a zone. The buzzer of the control unit emits a
two-note tone. The LCD display shows: A:ZONE nn
4. If you trigger a tamper alarm, the control unit display
shows: T:ZONE nn
5. To end the walk test, press:
199 Measuring the resistance
The alarm centre can measure the resistance values of the
zones and display them. You can therefore see if the right
resistors have been used. Proceed as follows:
1. On the control unit, enter:
2. The LCD display shows the values.
3. To change from zone to zone, press key 1 and key 3.
Meaning of display
Entry
Meaning
NO
No resistor used, zone open
2K1
2.2 KOhm resistor used
4K7
4.7 KOhm resistor used
...
Corresponding value in KOhm
To exit the program menu:
1. On the control unit, enter:
2. To exit the menu, press:
3. The control unit acknowledges your input with a long
"beep" tone and displays the date and time again.
.
097
.
.
199
.
099
.
87
991 Software version / Zone module check
Using this function, the installer can read out the software
version of the alarm centre and check whether the alarm
centre is partitioned.
1. On the control unit, enter:
2. The LCD displays the software version and the letter
for a partitioned system.
p
3. Once more press
expansion modules (max. 3).
To exit the programming menu, re-press
.
991
to check the connected
.
UK