Connecting expansion modules
The 8-zone wire expansion modules and the 8-zone radio
expansion modules are connected to the 4-wire bus as
follows.
UK
expansion modul
Make sure when connecting the 8-zone wire expansion
module that the zone terminations (CC / DEOL) from the
alarm centre and the expansion module are identical.
Addressing of expansion modules:
A determined range of zones must be assigned to each
expansion module. Two modules must not occupy the same
zone range. The zone ranges are addressed via the jumpers
on the expansion modules.
Walk test
The OP3 output must be appropriately programmed for the
walk test (function 83, option 5). If the user activates the walk
test function then the LED for motion detection is activated at
the detector.
motion detector 1
motion detector 2
walk test
walk test
Detector alarm memory
For the alarm memory function, e.g. for motion detectors, the
OP3 output must be appropriately programmed (function 83,
option 3). The first detector in the line that triggers the event
can store and signalise this.
motion detector 1
motion detector 2