4.9 Temperature sensor

FR
In case the temperature sensor is used, it must be connected to the T.SENSOR terminal. The
FR
EN
temperature sensor must be placed in the center of the battery bank. When the temperature sensor is
connected, the temperature compensation is 5mV/°C per element of 2 V (120 mV/°C for 48 V batteries).

4.10 Generator relay

The integrated relay allows to automatically start and stop the diesel generator via a dry contact
depending on the battery state of charge.
WARNING: The generator must be equipped with AVR (automatic voltage regulator) and
frequency control (pickup). The output of the generator must comply with the AC input voltage
specifications of the IMEON (N/PE =0 Vac) to be checked prior to connection to IMEON.
The generator will charge the batteries connected to the IMEON through the "GRID CONNECTION"
terminal as soon as the voltage of battery bank is below the "battery cut-off voltage when grid is
available" threshold. Then the generator will stop automatically. The generator will stop charging the
batteries until the battery pack is recharged.