4.8 Load (AC Output) connection

WARNING: It is very important for the safety and efficiency of the system to use the appropriate
AC connection cables.
WARNING: Please use maximal protections according to the existing standards (circuit
breaker, differential current breaker). The circuit breaker must protect against currents
exceeding the maximum output current of the inverter (17 A per phase). Use a circuit breaker
Type A 30mA.
Note: The inverter current (battery + PV) cannot exceed 13A nominal per phase. In the case of grid
outage, make sure not to go over this figure.
FR
Note: In case of the connection of PV only (grid outage and no battery), the AC OUTPUT of the
inverter will not be activated.
FR
EN
Note: To prevent further supply to the load via the inverters AC OUTPUT during any mode of
operation, an additional disconnection device should be placed in the buildings wiring
installation.
Step 1: Open the circuit breaker in order to work safely on the installation.
Step 2: Remove insulation sleeve and connect wires according to polarities indicated on the terminal
block. Be sure to connect PE protective conductor (
neutral (N), of the phases (L1, L2 and L3) and the ground ( ) wires.
Connect the phases to the symbol « L1, L2, L3 »
Connect the neutral to the symbol « N »
Connect the ground to the symbol «
106
IMEON 9.12
Guide de montage / Installation guide IMEON 9.12 – Rev A.8
) first. Respect the placement of the
»
2
3
1