IMEON ENERGY IMEON 9.12 Guide De Montage page 139

Masquer les pouces Voir aussi pour IMEON 9.12:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Close the circuit-
breaker located
E3
between the grid
and the inverter.
Open the circuit-
breaker located
E4
between the grid
and the inverter.
Connect the plug on
the «GRID
E5
CONNECTION»
socket of the
inverter.
Close the circuit-
breaker located
E6
between the grid
and the inverter.
Manuel d'installation / Installation guide IMEON 9.12 – Rev A.8
IMEON 9.12
Measure the voltages on the «GRID
CONNECTION» plug:
L1/N - L2/N and L3/N = 230 Vac
L1/Ground-L2/Ground and L3/Ground = 230 Vac
N/Ground= 0 Vac
If not, check the wiring.
Measure the voltages on the «GRID
CONNECTION» plug:
L1/N - L2/N and L3/N = 0 Vac
L1/Ground-L2/Ground and L3/Ground = 0 Vac
N/Ground= 0 Vac
When connecting the « GRID CONNECTION »
plug, ensure that the protections of the grid are
open.
Ensure that the connector is correctly set in place.
Check that the LCD display turns on.
FR
FR
EN
139