Load (Ac Output) Connection - IMEON ENERGY IMEON 3.6 Manuel D'installation

Masquer les pouces Voir aussi pour IMEON 3.6:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

IMEON INVERTER
3.8.2 Grid Connection for IMEON 9.12
WARNING: Check phase shift rotation clockwise L1, L2 and L3. In case of phase inversion, the
inverter will start but will not be synchronized with the public grid.
Connect the phases L1 to «L», L2 to «1» and L3
to «2».
Connect the neutral wire to the symbol « N »
Connect the Earth wire to the symbol «
2
3
Step 4: Make sure the wires are securely connected.
Step 5: Plug the RST connector in the GRID
CONNECTION socket.

3.9 Load (AC OUTPUT) connection

WARNING: It is very important for the safety and efficiency of the system to use the appropriate
AC connection cables.
WARNING: Please use maximal protection according to the existing standards (circuit breaker,
differential current breaker). The circuit breaker must protect against currents exceeding the
maximum output current of the inverter (17 A per phase). Use a circuit breaker Type A 30mA.
Note: The inverter current (battery + PV) cannot exceed 13A nominal per phase. In the case of grid
outage, make sure not to go over this figure.
Note: In case of the operation with PV only (grid outage and no battery), the AC OUTPUT of the
inverter will not be activated.
Note: To prevent further supply to the load via the inverters AC OUTPUT during any mode of
operation, an additional disconnection device should be placed in the buildings wiring
installation.