3.11 Temperature sensor

In case the temperature sensor is used, it must be connected to the T.CAP terminal. The temperature
sensor must be placed in the center of the battery bank. When the temperature sensor is connected, the
temperature compensation is 5mV/°C.

3.12 Generator relay

FR
FR
EN
ES
The integrated relay allows automatically starting and stopping the diesel generator via a dry contact
depending on the battery state of charge.
WARNING: The generator must be equipped with a voltage regulator and a frequency
regulator. The output of the generator must comply with the AC input voltage specifications of the
IMEON (N/PE =0 Vac) to be checked prior to connection to IMEON.
The generator will charge the batteries connected to the IMEON through the "GRID CONNECTION"
terminal as soon as the voltage of battery bank is below the "battery cut-off voltage when grid is
available" threshold. The generator will stop automatically. The generator will stop charging the
batteries when the battery pack is recharged.
In order to use this function, you need to go to IMEON OS. ONE, page "Module", then enable the "Genstart"
module and configure the module. It will auto-configure certain settings of the inverter. To learn more about
auto-configuration, refer to the module description.
74
Manuel d'installation / Installation guide IMEON Inverter/ Guia de montaje – Rev C.14