AC BACKUP short-circuits. Shutdown the inverter, then unplug the AC BACKUP connector,
then restart the inverter and activate the AC BACKUP by pushing the OK button during 3sec.
If this error is resolved, the issue comes from a connected device on the AC BACKUP
connector. If the problem remains, please contact your distributor.
Fan failure. Please restart the inverter. If the problem remains, please contact your
distributor.
AC BACKUP sensor failure. Please restart the inverter. If the problem remains, please
contact your distributor.
Hardware version detection error. Please restart the inverter. If the problem remains, please
contact your distributor.
AC Input/Output reversal. This problem may cause a critical electronic damage. Stop the
inverter and check the AC Grid and AC BACKUP connections are not reversed. If the
problem remains, please contact your distributor.
AC BACKUP undervoltage. Please reboot the inverter and activate the AC BACKUP. If the
problem remains, please contact your distributor.
AC BACKUP overvoltage. Please reboot the inverter and activate the AC BACKUP. If the
problem remains, please contact your distributor.
Battery voltage too high. This problem may cause a critical electronic damage. Disconnect
your battery and check if its specifications comply with inverter. If the problem remains,
please contact your battery distributor.
Battery not connected. Please connect the batteries and check if a breaker/fuse is not open
between inverter and batteries. If the problem remains contact your battery distributor.
Charging current error. Check battery settings and check the battery connection & voltage. If
the problem remains, please contact your distributor.
Battery voltage differs from communicated value. There is a communication problem
between inverter and battery BMS. Please reboot the battery and inverter and check the
good connection of battery communication cable. If the problem remains, please contact
your distributor.
Internal supply failure. Please restart the inverter. If the problem remains, please contact
your distributor.
CAN communication lost. There is a communication problem between inverter and battery
BMS. Please reboot the battery and inverter and check the good connection of battery
communication cable. If the problem remains, please contact your distributor.
Battery error reported. Check the battery ID error in OS. ONE, then restart the battery and
the inverter. If the problem remains contact your battery distributor.
Communication lost between processors. Please reboot the inverter. If the problem remains,
please contact your distributor.
Internet connection lost. Check your internet connection.
Battery current exceeds max battery current limit. Please check the good setting of battery
parameter in OS. ONE. If the problem remains contact your battery distributor.
Power on grid connection overpasses maximum power specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
Current on grid connection overpasses maximum power specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
Frequency on AC BACKUP exceeds minimum frequency specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
Frequency on AC BACKUP exceeds maximum frequency specification. Please check the
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
Current on AC BACKUP overpasses maximum current specification. Remove the high
power devices with inrush power (air conditioner, pumps,...). This problem can cause a
critical electronic damage. If the problem remains contact your distributor.
PV input power overpasses specification. This problem can cause a critical electronic
damage. Please check the PV sizing, connection and installation. If the problem remains
contact your distributor.