UK | 9 Mounting

9 Mounting

9.1 Mounting instructions

● For WRG operation (air extraction and venti-
lation in a 60-second cycle), set up unit pairs.
● The room air control has plug-in connection
terminals, which can be taken off for wiring.
● When using more than 2 ventilation units,
we recommend installing the room air cont-
rol in an electronic switch box to be supplied
by the customer. This provides sufficient
space for the connection of the cables to the
room air control.
● Only mount internal covers on flat surfaces
and without any distortion to avoid noise.
● Prescribed connection cables,
also see wiring diagrams in appendix
Mains connection and 230 V input:
Type NYM-J 5G1, 5 mm²
Control cables: Type J-YSTY, 0.8 mm,
4 wires. Max. 25 m from star point, up to
star point max. 4 m.
● Connector plug for fan cable:
PP 45 O
Connect enclosed connector
plugs after line feedthrough in accordance
with wiring diagram.
PP 45 K
PP 45 RC
or 230 V power supply in accordance with
wiring diagram in appendix. Connector plug
for fan cable is plugged onto board.
● Ventilation units may only be operated using
the voltage and frequency shown on the
rating plate. For rating plate, see RLS 45 O
or RLS 45 K control or PP 45 RC ventilation
unit. Operating voltage for PP 45 O/K units
= 12 V DC.
● The appropriate mounting material must be
supplied on site.
● Sensors: Incorrect measured values can re-
sult from unsuitable installation location. Avoid
disturbing influences and direct sunlight.
36
Wire control input and/
● Disbalance may arise if the maximum stat-
ed cable lengths are exceeded. Observe
installation requirements relating to cable
lengths and types.
PP 45 O
PP 45 K
9.2
module and internal cover
Wall sleeves, external covers or soffit
i
elements are already installed in accor-
dance with shell mounting instructions.
1. Switch off mains fuse, affix warning sign
in visible location to prevent it from being
started up again.
Perform following steps for all ventilation
units
2. Take inner plaster protective cover out of
wall sleeve.
3. Check angle of inclination of fitted wall
sleeve. There must be an inclination of
1 to 2 % to the external wall.
4. Route control cables of ventilation units,
sensors and accessory components in the
empty ducts.
5. Take off front cover of internal cover's
housing. To do this, press on locking lever
on underside of housing and take off cover.
PP 45 O
6. With
and
the room air control's 12 V control cable
from the rear into the internal cover's
internal housing.
PP 45 RC
7. With
units, route the 230 V
power cable from the rear into the internal
cover's internal housing.
8. Align housing of internal covers horizon-
tally on the wall sleeve, mark the 4 fixing
holes, position dowels and screw down
housing to internal wall with 4 screws.
Suitable mounting material is to be sup-
plied by the customer. For drilling distan-
ces of internal cover  Appendix.
Fan unit, ceramic heat exchanger and
i
filter seats with the two air filters are
already inserted in the slide-in module
in the factory. G2 filter facing internal
wall, G3 filter facing external wall. For
filter types  Operating instructions,
Chapter 10.