UK | 10 Start-up
PP 45 RC LEDs
The blue operating
mode LED flashes
twice per cycle
The blue operating
mode LED flashes
three times per cycle
The blue operating
mode LED flashes
four times per cycle
50
Parameter
Set value
Sleep
1
2
function
3
Filter runtime 1
2
3
4
Single-room
1
ventilation
2
unit
Setting / description
30 minutes (red LED once)
60 minutes (red LED twice)
90 minutes (red LED three times)
Parameters for the duration of the
sleep function (level 0) are set
here (factory setting 60 minutes).
2 months (red LED once)
3 months (red LED twice)
6 months (red LED three times)
Reset filter runtime (red LED four
times)
Parameters for the filter run time
are set here (factory setting
6 months).
Operation in pairs
(red LED 1x)
single-room ventilation unit
(red LED 2x)
The configuration of the
PP45 RC unit as a single-room
ventilation unit is released here.
Recommendation: Do not use
PP 45 RC units as single-room
ventilation units because the
DIBt approval will thereby cease
to apply.
If a PP 45 RC is used as a
single-room ventilation unit, the
volumetric flow compensation
must be undertaken using external
wall air openings (ALDs). This has
a negative impact on the degree of
heat provision.