UK | 10 Start-up

10 Start-up

Basic settings on the room air control are
undertaken in service mode. If connected to
RLS 45 K, the commissioning software may
also be used.
Switch on ventilation system as follows:
Ensure that all ventilation units and system
components are connected to the room air
controls.
Remove warning sign from fuse box and
switch on mains fuse. The ventilation units
start up in ventilation level 2.
Run function test.
Set the desired parameter values in service
mode or using the commissioning software.
Basic settings can be undertaken
i
directly on the RLS 45 O or RLS 45 K
room air control.
To do this, select service mode and
set the desired parameter value. Addi-
tional information can be found in the
online commissioning instructions
(download from www.maico-ventila-
toren.com).
Here you can also download the com-
missioning software for the RLS 45
K control. This provides a large num-
ber of setting parameters for individual
system adaptations.
42
10.1 Service mode – operation
Starting service mode
Press both
+
buttons for
5 seconds.
+
+
Cycle: selecting parameter
You can
switch be-
tween the
sub-menus
/
by pressing
the button
once.
* Illuminated ventilation level LEDs indicate
the parameter currently set.
** For PP45 RC, the red flashing LED indi-
cates the parameter currently set.
Operating mode
LED flashes. You
are in the 1st
sub-menu
(number of unit
pairs, ventilation
level etc.)
Chap. 10.2 to
10.4
.
Flashing ope-
rating mode LEDs
indicate
the current sub-
menu item */**
 Chap. 10.2
to 10.4
.