2.3. STRUCTURE (WING 100-200)
WING W100-200 – WATER AIR CURTAIN
1. Heat exchanger
2. Control system
3. Transverse fan
4. Casing
5. Outlet grille
6. Assembly jigs
7. Side cover
8. Side cap
1. HEAT EXCHANGER – WATER HEATER: Maximum parameters of the heating agent for the heat exchanger are: 95°C, 1.6MPa. The aluminium and copper construction consists of copper
pipes of the coil and aluminium lamellae. The connection manifold (¾`` male thread) is situated in the upper part of the housing. An optimally selected water exchanger was adapted to work in
three positions: horizontally and vertically, with stub pipes facing upwards and downwards. Appropriate lead of hydraulic connections makes it possible for the curtain to be assembled directly by
the wall as close to the door frame as possible. The air curtain with a water heater generates power from 4 to 47 kW.
ELECTRIC HEATER: each electrical curtain consists of 6 electrical heaters of 670W to 2950W, depending on the size of the curtain. The heaters are connected into two sections of 2 and 4 kW
for a 1m curtain, 4 and 8 kW for a 1.5m curtain, and 6 and 9kW for a 2m curtain. The heating section is connected to form a 3x400V power supply star. There is a possibility of powering a 1m
curtain with 1x230V for a 2kW heater.
Thanks to such technical solutions and the application of a wall-mounted controller, the heater of each curtain can work in two heating programmes, e.g. for a WING E100 curtain - option
1): heating programme 1 - 2kW, heating programme 2 - 4kW, option 2): programme 1 - 4kW, programme 2 - 6kW, and analogously for the remaining curtain sizes. Change of programme is
displayed on the diagram and consists in a cable switch in controller WING/VOLCANO (AC) or HMI-WING EC. The heating programme is independent from the fan speed setting.
2. CONTROL SYSTEM: it is equipped with an outlet on the connection clamp block X0 for WING W100-200 and on the X1 block for WING E100-200 for connecting an on-wall controller as well
as a valve actuator for WING W100-200. WING air curtains can be additionally equipped with a wall-mounted WING/VOLCANO (AC) or HMI-WING EC controllers. The WING/VOLCANO
(AC) controller has a three-position heating switch. In the case of a water curtain, to guarantee the proper functioning of the water valve, the heating switch must be set to position II (central) -
otherwise the valve will not open.
The system of WING E100-200 is equipped with a safety device in the form of a fuse in the 230 V AC circuit. HMI-WING EC controller enables three-position regulation of rotational speed of the
fans with EC motors, as well as two-position regulation of the heating power.
3. HORIZONTAL FAN: the maximum temperature of operation is 95°C, the rated voltage is 230 V/50 Hz. The motor protection level is IP20, F insulation class. The horizontal fan applied in the device
with an advanced profile of blades and impeller geometry made of plastic makes it possible to obtain air capacities up to 4600 m
of the winding has been coupled with the control system which resulted in increasing safety of operation. Due to optimum power of the motor the WING curtain is energy saving and durable.
4. CASING: Made of metall material resistant to temperature up to 95°C.
5. INSTALLATION HANDLES: WING is characterized by simple, quick and aesthetic assembly that can be performed on a wall in both horizontal and vertical position. There are from 2
to 3 installation handles attached (as an option) to the curtain (depending on the option (length)). Connections of electric wires and water channels has been especially designed not
to interfere the general aesthetic values of the device. The name WING includes devices that are 1, 1.5 and 2 m long that, if necessary, can be additionally joined both horizontally and
vertically to achieve different air supply options: from the left to the right and the opposite. the reach of the air stream is up to 4 m.
IMPORTANT! Possibility of the vertical assembly applies only to the cold curtains and with water heater. Curtains with electric heaters may only be installed in a horizontal position.
2.4. OVERALL DIMENSIONS (WING E, W, C 100-200)

3. ASSEMBLY

IMPORTANT!
● The place of assembly should be carefully selected, taking into account the occurring of potential loads or vibrations.
● Prior to all installation or maintenance work, disconnect power supply and secure it against unintentional reactivation.
● It is recommended to use filters in the hydraulic system. It is recommended to clean/rinse the system, draining a few litres of water, prior to the connecting of hydraulic conduits (the supply
conduits, in particular).
IMPORTANT!
The air is blown out of the curtain at high velocity, along the surface of the opening, thus creating a protective barrier. Air curtains should cover the entire width of the door opening, in order to
obtain the maximum performance of the curtain.
IT IS RECOMMENDED TO TAKE INTO ACCOUNT THE FOLLOWING PARAMETERS, WHEN ASSEMBLING THE CURTAIN:
The width of the door frame should be less or equal to the width of the supplied air stream.
WING E100-200 – ELECTRIC AIR CURTAIN
1. Electric heaters
2. Control system
3. Transverse fan
4. Casing
5. Outlet grille
6. Assembly jigs
7. Side cover
8. Side cap
WRONG
WING C100-200 – COLD AIR CURTAIN
³
/h. The control of the electric motor as well as thermal protections
CORRECT
25
1. Control system
2. Transverse fan
3. Casing
4. Outlet grille
5. Assembly jigs
6. Side cover
7. Side cap
EN