Colonia 3 - Mini Colonia
English
DO NOT install the cabinet:
in rooms with explosion hazard
outdoors exposed to atmospheric agents
near heat sources (direct sunlight, heating systems, incandescence lamps, etc.)
in the vicinity of air currents (close to doors, windows, air-conditioning systems, etc.)
that exceed a speed of 0,2 m/s
14. Electric connection
DANGER! Live parts. Electrocution
REMOVE THE ELECTRIC POWER SUPPLY BEFORE ANY OPERATION!
- ensure that the casing does not come into contact with the electrical panel
- verify that the connections of the various illuminations (floor, roof, over-structure)
are correctly inserted and secured in the respective sockets to avoid disconnections
during cleaning and maintenance
Install an adequate grounding system!
i
Implement the systems in accordance with the directives that govern construction,
installation, use and maintenance provided in accordance with the standards in force in
the country of installation.
To ensure smooth operation, maximum voltage variation must be between +/-6% of the
nominal value.
Liability
Customer
Installer
ARNEG
Line of
size the electricity supply lines according to the power consumption of the
power supply
i
Automatic
safety switches
instruct the operator on the position of the switches to be reached quickly
38
install the electrical power supply line to the point of
connection of the cabinet.
the installer must provide the anchoring devices for all the
wires in input and output to/from the cabinet.
ARNEG S.p.A. declines any liability in relation to the user
and any third party arising from:
- damage caused by accidents or malfunctions of the
systems installed upstream of the cabinet
- damage caused to the cabinet due to causes directly
attributable to malfunctions of the electrical system
cabinet (cap.9.).
check that the power line.
- has adequate section cables
- is protected against overcurrents and dispersions to ground in
accordance with the standards in force
for power lines longer than 4-5 m appropriately increase the cable section
Replacement of the power cable is reserved to the manufacturer or to
a body designated by it.
protect the cabinets upstream with automatic omni-polar thermal-
magnetic circuit breakers with adequate characteristics that also have the
function of line-sectioning general switches.
in case of EMERGENCY
DANGER! Live parts. Short circuit. Electrocution
The automatic magneto-thermal switches must be such that they do
not open the circuit on the neutral, without simultaneously opening
on the phases and, in any case, the distance between the opening of
the contacts must be at least 3 mm.