Signal targets for STW1 in Interface Mode VIK-NAMUR (p2038 = 2)
Signal
Meaning
= ON (pulses can be enabled)
STW1.0
0 = OFF1 (braking with ramp-function generator, then pulse cancllation & ready-to-power-up)
1 = No OFF2 (enable is possible) <3>
STW1.1
0 = OFF2 (immediate pulse cancellation and power-on inhibit)
1 = No OFF3 (enable possible) <3>
STW1.2
0 = OFF3 (braking with the OFF3 ramp p1135, then pulse cancellation and power-on inhibit)
1 = Enable operation (pulses can be enabled)
STW1.3
0 = Inhibit operation (cancel pulses)
1 = Operating condition (the ramp-function generator can be enabled)
STW1.4
0 = Inhibit ramp-function generator (set the ramp-function generator output to zero)
1 = Enable the ramp-function generator
STW1.5
0 = Stop the ramp-function generator (freeze the ramp-function generator output)
1 = Enable setpoint
STW1.6
0 = Inhibit setpoint (set the ramp-function generator input to zero)
STW1.7
= Acknowledge faults
STW1.8
Reserved
STW1.9
Reserved
STW1.10
1 = Control via PLC
<2>
STW1.11
1 = Direction reversal
STW1.12
Reserved
STW1.13
Reserved
STW1.14
Reserved
STW1.15
1 = CDS selection
<1> Used in telegram 20.
<2> STW1.10 must be set to ensure that the drive object accepts the process data (PZD).
1
2
DO: VECTOR
PROFIdrive - STW1 control word interconnection (p2038 = 2)
Interconnection
parameters
p0840[0] = r2090.0
p0844[0] = r2090.1
p0848[0] = r2090.2
p0852[0] = r2090.3
p1140[0] = r2090.4
p1141[0] = r2090.5
p1142[0] = r2090.6
p2103[0] = r2090.7
p0854[0] = r2090.10
p1113[0] = r2090.11
p0810[0] = 2090.15
<3> OC = Operating condition.
<4> Interconnection is not disabled.
3
4
[Function diagram]
[Function diagram]
internal control word
signal target
[2501.3]
[2610]
[2501.3]
[2610]
[2501.3]
[2610]
[2501.3]
[2610]
[2501.3]
[3060] [3070] [3080]
[2501.3]
[3060] [3070]
[2501.3]
[3060] [3070] [3080]
[2546.1]
[8060]
-
-
-
-
-
-
[2501.3]
[2501]
[2505.3]
[3040]
-
-
-
-
-
-
-
-
-
<4>
-
[8560]
5
6
Function diagram
fp_2441_54_eng.vsd
S120/S150/G130/G150
14.08.08 V04.03.01
PROFIdrive sampling time
<1>
Refer to [1020.7]
Inverted
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7
8
- 2441 -