4.3) Learning the door opening and closing positions

After self-learning the devices, the control unit must recognise the door opening and closing positions, as well as a total of six other option-
al positions:
Position
led
Meaning
FCA
L1
Maximum opening position. When the door reaches this position it stops
RA
L2
Deceleration start position during the opening manoeuvre; when the door reaches this position the motor decelerates to
the minimum speed.
RI
L4
Intermediate deceleration position in closing manoeuvre. When this point is programmed, the door starts to decelerate at
approx. 50 cm beforehand, to pass from the position RINT to minimum speed. On passing the RINT position the motor
returns to the set speed
AP
L5
Partial opening position. This is the position at which the door stops after receiving a partial opening command.
RC
L7
Deceleration start position during the closing manoeuvre; when the door reaches this position the motor decelerates to
the minimum speed.
FCC
L8
Maximum closing position; when the door reaches this position it stops
When the positions have not been acquired, leds L3 and L4 flash.
The position memorisation procedure is described below. Positions FCA and FCC require compulsory programming, while the others remain
optional; if not programmed the latter are calculated automatically by the control unit.
1.
Press [Set] + [▼] for 3 seconds to enter position memorisation mode. (Figure 21)
Led L1 flashes: Position FCA programming
2.
Use keys [▲] or [▼] to move the door to the opening position.
3.
Press [Set] for 2 seconds to confirm position FCA. Led L1 remains lit
Led L2 flashes: Position RA programming
4.
If the opening slowdown position programming is not required, press the key [Set] twice quickly to skip to the next programming;
led L2 remains off. Otherwise proceed with the sequence
5.
Use keys [▲] or [▼] to move the door to the opening deceleration position.
6.
Press [Set] for 2 seconds to confirm position RA. Led L2 remains lit
Led L4 flashes: Position RI programming
7.
If the intermediate slowdown position programming is not required, press the key [Set] twice quickly to skip to the next
programming; led L4 remains off. Otherwise proceed with the sequence
8.
Use keys [▲] or [▼] to move the door to the intermediate deceleration position.
9.
Press [Set] for 2 seconds to confirm position RI. Led L4 remains lit
Led L5 flashes: Position AP programming
10.
If the partial opening position programming is not required, press the key [Set] twice quickly to skip to the next programming; led
L5 remains off. Otherwise proceed with the sequence
11.
Use keys [▲] or [▼] to move the door to the partial opening position.
12.
Press [Set] for 2 seconds to confirm position AP. Led L5 remains lit
Led L7 flashes: Position RC programming
13.
If the closing slowdown position programming is not required, press the key [Set] twice quickly to skip to the next programming;
led L7 remains off. Otherwise proceed with the sequence
14.
Use keys [▲] or [▼] to move the door to the closing deceleration position.
15.
Press [Set] for 2 seconds to confirm position RC. Led L7 remains lit
Led L8 flashes: Position FCC programming
16.
Use keys [▲] or [▼] to move the door to the closing position.
17.
Press [Set] for 2 seconds to confirm position FCC. Led L8 remains lit.
18.
On release of [Set] all leds turn off.
19.
Give an open command by pressing [Open] to execute a complete opening manoeuvre.
20.
Give a close command by pressing [Close] to execute a complete closing manoeuvre.
During these manoeuvres, the control unit memorises the force
required for the opening and closing movements.
It is important that these preliminary manoeuvres are not
interrupted for example by a STOP command.
The position learning phase can be repeated at any time also after
installation, by simply repeating the procedure from point 1. Howev-
er, if only one position needs to be modified, skip programming of
the positions not involved by pressing the key [Set] twice quickly for
each position to skip.