7.2.1) Level 1 programming (ON-OFF functions)

Table 8: List of programmable functions: Level 1
Led Function
L1
Automatic closure
L2
Re-close After Photo
L3
Always Close
L4
Stand-By
L5
Long inversion
L6
Pre-flash
L7
Sensitivity
L8
2 motors
During normal operation of TEN, i.e. when no manoeuvre is in progress, leds L1....L8 are lit or off depending on the status of the associated
function, for example L1 is lit if the function "Automatic closure" is enabled.
During the manoeuvre, leds L1...L8 flash, indicating the force required to move the door at that time. If L8 flashes, the force required is
minimal, and so on through to L1 which indicates the maximum force level.
Note that there is no relation between the force level indicated by the leds during movement (an absolute value) and the level indicated by
the leds during force programming (a relative value). See L5 and L6 in table 10.
7.2.2) Level 1 programming (ON-OFF functions)
By default level 1 function are all set to OFF, but can be modified at any time as described below. Take care during modification procedures,
as there is a maximum time interval of 10 seconds between pressing one key and another; otherwise the system exits the procedure auto-
matically memorising the changes made up to that time.
Table 9: To change the ON-OFF functions
1.
Press and hold [Set] for approx. 3s
2.
Release the key [Set] when led L1 starts to flash
3.
Press keys [▲] or [▼] to move the flashing led to the led associated with the function to be modified
4.
Press [Set] to change the status of the function (short flash = OFF; long flash = ON)
5.
Wait 10s to exit the programming mode automatically after the maximum time interval
Note: points 3 and 4 can be repeated during the same programming phase to set other functions to ON or OFF
Description
This function enables automatic closure of the door after a programmed pause; the default Pause Time is
set at 30 seconds but may be modified to 10, 20, 40, 60, 80, 120, 160 or 200 seconds.
If the function is not enabled, operation is set to "semi-automatic"
This function enables the door to remain open only for the time required for transit; in fact activation of
"Photo" always activates automatic re-closure with a pause time of 5 seconds (regardless of the set value)
Operation depends on whether the "Automatic Closure" function is enabled or not.
With "Automatic closure" not active: The door always reaches the total opening position (even if
Photo is disengaged beforehand). On disengagement of Photo, automatic re-closure is activated with a
pause of 5 seconds.
With "Automatic closure" active: The opening manoeuvre is stopped immediately after the photocells
are disengaged and automatic re-closure is activated with a pause of 5 seconds.
The function "Re-close After Photo " is always disabled in manoeuvres interrupted by a Stop command.
If the function " Re-close After Photo " is not active, the pause time is as programmed and there is not
automatic re-closure if the function is not active.
The function "Always Close" is activated, activating closure, when power is restored and the door is
detected as open.
For safety reasons, the manoeuvre is preceded by a 3-second pre-flashing interval.
If the function is not active, on power restoral the door remains stationary.
This function enables a reduction of consumption to a minimum. If this function is active, after 1 minute
from the end of the manoeuvre, the control unit turns off the BlueBUS output (and therefore all connected
devices) and all leds, except for the BlueBUS led, which flashes at a slower interval. When the control unit
receives a command it restores normal operating conditions. If the function is not active there is no
reduction in consumption.
This function enables the user to select the type of inversion that the door performs on receipt of command
from STOP or the force limiter. If the function is not active, inversion is short (approx. 15 cm). If the function
is active, inversion is activated through to the maximum opening or closing position.
When the pre-flash function is active, a pause of 3 seconds is added between start-up of the flashing light
and the start of the manoeuvre, to give advance warning of a hazardous situation. If pre-flash is not active
the flashing light is started at the same time as the manoeuvre.
This function enables a significant increase in motor sensitivity in obstacle detection. If used as an aid for
reading impact force, the parameters "Speed" and "Motor Force" in the level 2 menu should also be set
accordingly.
This function must be enabled when the installation is with 2 motors.
GB
Example
SET
3s
SET
L1
or
SET
10s
17