9.3.1 Procedure in the case of fan failure
Danger to life from electric
shock.
DANGER
Never touch live components.
1. Check the function of the door contact
switch [7]. Replace this if necessary.
If the front door is closed (door
contact switch [7] is activated), there
is a 230 V AC supply voltage to the
terminal pairs "X" and "Y" of the "A2"
control circuit board  Chapter 6.7
Electrical connection.
2. With the door contact switch [7] actuated,
check the 230 V AC exhaust air and
supply air fan supply voltage to the
terminal pairs "X" and "Y".
3. Delete the fault message as described in
Chapter 9.1.
The 1.7 to 10 V DC fan control voltage is then
present for around 1 minute on the plug pins
of the "A2" control circuit board.
The fault message now appears again.
9. Faults, messages │ uk
4. Check the supply air and exhaust fan
control voltage at the plug pins: supply air
side on pins 1 and 3, exhaust air side on
pins 5 and 3.
5. The control voltage for both the supply
air and exhaust fan is in each case
1.7...10 V DC.
6. Replace the circuit board or fans if
necessary
9.3.2 Temperature sensor fault
The ventilation unit goes into fault mode if the
internal frost protection temperature sensor
fails (short-circuit, cable break or because it is
not connected).
Both fans switch off immediately. The fault
message on the room air control goes out
after approx. 1 minute (no LED lit up any
more), both fans remain switched off.
69