uk │ 6. Installation ‒ Connection options
6.10 Connection option 3: WS 170
with RLS 1 WR or RLS D1 WR
and external operating display
Refer also to the wiring diagram in the
appendix
A
WS 170 electronic slide-in module
A2
Control circuit board: Jumper 8
bridged (= factory setting)
B
RLS D1 WR room air control
B1
RLS 1 WR room air control
H1
Display element, e.g. glow lamp (to
be supplied by the customer)
W1
230 V AC connection cable
W2, W2´ Control cable for room air control
W3
Cable for an external operating
display (to be supplied by the
customer). The connection on
A2 control circuit board is done
at the "Operating display" terminal.
60
An operating display (lamp, contactor, etc.)
can be connected to the control circuit board
for an external monitoring of the ventilation
unit by a building supervisor, for example.
The "k1" potential-free relay contact can be
found on the control circuit board for this
purpose.
Relay contact "k1" is closed when
the ventilation unit is running.
The maximum load-bearing capacity
for relay contact k1 = 3A / 250 V AC,
2A / 30 V DC