Classification No.
E025
E026
Electronic
E030
module error
E031
E032
E033
E035
Communica-
E050
tion errors
E051
E052
Electronics
E070
errors
E071
E072
E073
E075
E076
E077
E078
E096
E097
E098
E110
E111
E112
Installation and operating instructions Wilo-Stratos GIGA, GIGA-D, GIGA B
Fault
Cause
Faulty contact
Electronic module has no
contact to motor
Winding interrupted
Motor faulty
WSK or PTC
Motor faulty
interrupted
Excess electronic
Limited air supply to the
module temperature
heat sink of the
electronic module
Excess temperature,
Ambient temperature too
hybrid/power section
high
Intermediate circuit
Voltage fluctuations in
undervoltage
the mains
Intermediate circuit
Voltage fluctuations in
overvoltage
the mains
DP/MP: multiple
Multiple instances of
instances of same
same identity
identity
BMS communication
Bus communication
timeout
interrupted or timed out
Cable break
Impermissible DP/MP
Different pumps
combination
DP/MP
Cable MP communication
communications
defective
timeout
Internal
Internal electronics error* Request customer service
communication error
(SPI)
EEPROM error
Internal electronics error
Power section/
Internal electronics error
electronic module
Impermissible
Internal electronics error* Request customer service
electronic module
number
Charging relay
Internal electronics error
defective
Internal transformer
Internal electronics error
defective
24 V operating voltage
Differential pressure
for differential
sensor defective or
pressure sensor
connected incorrectly
defective
Impermissible motor
Internal electronics error
number
Infobyte not set
Internal electronics error
Flexpump data record
Internal electronics error
missing
Flexpump data record
Internal electronics error
invalid
Motor synchronisation
Internal electronics error
error
Excess current
Internal electronics error
Excess rotation speed Internal electronics error
Remedies
Request customer service
Request customer service
Request customer service
Provide unobstructed air
access
Improve room ventilation
Check electrical installation
Check electrical installation
Reallocate master and/or slave
(see chapter 9.2 "Twin-head
pump installation/ Y-pipe
installation" on page 112)
Check cable connection to
building automation
Request customer service
Check cable and cable
connections
Request customer service
Request customer service
Request customer service
Request customer service
Check differential pressure
sensor connection
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
(11-22kW)
English
Error type
HV
AC
A
A
B
A
B
A
B
A
F
D
F
D
E
E
F
F
F
F
E
E
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
B
A
B
A
B
A
123

Publicité

Table des Matières
loading

Table des Matières