Commissioning - Wilo Stratos GIGA Série Notice De Montage Et De Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

No.
Designation
5.8.1.1 Pump kick active/
inactive
5.8.1.2 Pump kick
Time interval
5.8.1.3 Pump kick
Speed
6.0.0.0
Fault
acknowledgement
7.0.0.0
Access disable
Tab. 8: Menu structure
9

Commissioning

Safety
Preparation
Installation and operating instructions Wilo-Stratos GIGA, GIGA-D, GIGA B
Type
Symbol Values/explanations
±
ON (factory setting)
Pump kick is activated
OFF
Pump kick is deactivated
±
Can be set between 2 h and 72 h
in 1 h steps
±
Can be set between the pump's
minimum and maximum speeds
±
For additional information, see
chapter 11.3 "Acknowledging
errors" on page 125
±
"Access disable" inactive
(changes possible)
(for further information,
see chapter 8.6.7 "Activating/
deactivating access disable" on
page 103)
"Access disable" active
(no changes possible)
(for further information,
see chapter 8.6.7 "Activating/
deactivating access disable" on
page 103)
DANGER! Risk of fatal injury!
Failure to install safety devices of the electronic module and the
motor can cause electrical shock or contact with rotating parts,
potentially resulting in life-threatening injuries.
• Before commissioning as well as after maintenance work, all safety
devices such as module covers and fan covers that were removed
must be reinstalled.
• Keep a safe distance during commissioning.
• Never connect the pump without the electronic module.
Before commissioning, the pump and electronic module must be at
the ambient temperature.
(11-22kW)
English
Display conditions
Is not displayed if pump kick
is deactivated
Is not displayed if pump kick
is deactivated
Only displayed if an error is
present
111