12. ALARM SIGNALLING

Message Cause
Outputs
"P1"
Thermostat probe failure
Compressor and heating outputs off
"P2"
Evaporator probe failure
Defrost and by time
"P3"
Humidity probe failure
Humidity regulation off
"HA"
High temperature alarm
Outputs unchanged
"LA"
Low temperature alarm
Outputs unchanged
"HHA"
High humidity alarm
Outputs unchanged
"HLA"
Low humidity alarm
Outputs unchanged
"dA"
Door switch alarm
Outputs depending on the odC parameter
"EAL"
External alarm
Other outputs unchanged
"BAL"
Serious external alarm
Outputs OFF
"PAL"
Pressure switch alarm
Outputs OFF
The alarm message is displayed until the alarm condition recoveries.
All the alarm messages are showed alternating with the room temperature except for the "P1" which is
flashing. To reset the "EE" alarm and restart the normal functioning press any key, the "rSt" message is
displayed for about 3s.
12.1 SILENCING BUZZER
Once the alarm signal is detected the buzzer, if present, can be silenced by pressing any key.
12.2 ALARM RECOVERY
Probe alarms : "P1" (probe1 faulty), "P2", "P3"; they automatically stop 10s after the probe restarts
normal operation. Check connections before replacing the probe.
Temperature alarms "HA" and "LA" automatically stop as soon as the thermostat temperature returns to
normal values or when the defrost starts.
Humidity alarms "HHA" and "LHA" automatically stop as soon as the humidity returns to normal values.
Door switch alarm "dA" stop as soon as the door is closed.
External alarms "EAL", "BAL" stop as soon as the external digital input is disabled
Pressure switch alarm "PAL" alarm is recovered by switching OFF the instrument.

13. TECHNICAL DATA

Housing: self extinguishing ABS.
Case: XH260L: facia 38x185 mm; depth 76mm; XH260V: facia 100x64 mm; depth 76mm
Mounting: XH260L: panel mounting in a 150x31 mm panel cut-out with two screws.
Distance between the holes 165mm
XH260V: panel mounting in a 56x72 mm panel cut-out with two screws.
between the holes 40mm
Protection: IP20.
Frontal protection: IP65 with optional frontal gasket mod. RG-L (XH260L); RGW-V (XH260V)..
Connections: Screw terminal block
2,5 mm
Power supply: 230Vac or 110Vac
10%; Power absorption: 7VA max.
±
Display: double display + icons.
Inputs: 1 NTC probe + 4÷20mA probe
Digital input: 1 free voltage
Relay outputs: compressor:
XH260L: relay SPST 20(8) A, 250Vac;
XH260V: relay SPST 8(3) A, 250Vac
heather: relay SPST 8(3) A, 250Vac; defrost: relay SPST 8(3) A, 250Vac
fans: relay SPST 8(3) A, 250Vac; humidifier: relay SPST 8(3) A, 250Vac
de-humidifier: relay SPST 8(3) A, 250Vac
Other output : alarm buzzer (optional)
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B.; Pollution grade: normal; Software class: A.
Operating temperature: 0÷60 °C.; Storage temperature: -25÷60 °C.
Relative humidity: 20
÷
85% (no condensing)
Measuring and regulation range:
NTC probe: -40÷110°C (-58÷230°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit

14. WIRING CONNECTIONS

14.1 XH260L
8(3)A
8(3)A
8(3)A
8(3)A
8(3)A
20(8)A
250V~
250V~
250V~
250V~
250V~
250V~
1
2
3
4 5
6
7
8
9 10
11
12 13
NC
Fan
Def
Comp
Heater
Hum
Supply 115Vac: 14-15 terminals
14.2 XH260V
Hum
Supply 115Vac: 2-3 terminals
1592002711 XH260L-V GB r1.0 23.03.2015
3x2mm. Distance
2
heat-resistant wiring and 6,3mm Faston
14 15
16
17
18 19
20
21 22 23
N
L
C
N.C.
Fan
Def
Comp
MAX
20A
8(3)A250V~
Heater
15. DEFAULT SETTING VALUES
Label
Value Menu
Set T
5.0
Set H
50.0
dbt
2.0
dbH
5.0
LS
-40
uS
110
odS
1
Ac
1
tHu
db
LSH
0.0
uSH
100.0
cF
°C
rES
dE
rEH
Hd
tdf
rE
EdF
in
SdF
0
dtE
8
idF
8
MdF
20
dFd
it
dAd
30
Fdt
0
dPo
no
Hud
no
Fnc
c-n
ALc
Ab
ALL
-40.0
ALu
3 x 2mm.
110
ALH
1.0
ALd
15
dAo
1.3
EdA
20
dot
20
AHc
Ab
AHL
0.0
AHu
100
AHH
2.0
AHd
15
dHo
1.3
doH
20
nPS
0
doA
20
ot
0.0
oE
0.0
o3
0.0
P2P
no
P3P
YES
Lci
0
uci
100
i1P
oP
i1F
dor
odc
oFF
rrd
YES
did
0
oA1
Lig
Adr
1
Ptb
1
rEL
0.1
Prd
--
Pr2
321
XH260L - XH260V
Description
- - -
Temperature Set Point
- - -
Humidity Set Point
Pr1
Half dead band width for temperature
Pr1
Half dead band width for humidity
Pr2
Minimum temperature set point limit
Pr2
Maximum temperature set point limit
Pr2
Outputs activation delay at start up
Pr1
Anti-short cycle delay
Pr2
Humidity regulation
Pr2
Minimum humidity set point limit
Pr2
Maximum humidity set point limit
Pr2
Measurement unit
Pr2
Resolution (for °C):
Pr2
Resolution for RH%:
Pr2
Defrost type
Pr2
Defrost mode
Pr2
Set point for SMART DEFROST
Pr2
Defrost termination temperature
Pr1
Interval between defrosts
Pr1
Duration of defrost
Pr2
Display during defrost
Pr2
Defrost display time out
Pr2
Draining time
Pr2
First defrost after start up
Pr2
Humidity control during defrost
Pr2
Fan operating mode
Pr2
Temperature alarm configuration
Pr1
Low temperature alarm setting
Pr1
High temperature alarm setting
Pr2
Temperature alarm recovery differential
Pr2
Temperature alarm delay
Pr2
Delay of temperature alarm at start-up
Pr2
Alarm delay at the end of defrost
Pr2
Delay of temperature alarm after closing the
door
Pr2
Humidity alarm configuration
Pr1
Low humidity alarm setting
Pr1
High humidity alarm setting
Pr2
Humidity alarm recovery differential
Pr2
Humidity alarm delay
Pr2
Delay of humidity alarm at start-up
Pr2
Alarm delay at the end of defrost
Pr2
Pressure switch number
Pr2
Open door alarm delay
Pr1
Thermostat probe calibration
Pr2
Evaporator probe calibration
Pr1
Humidity probe calibration
Pr2
Evaporator probe presence
Pr2
Humidity probe presence
Pr2
Readout with 4 mA
Pr2
Readout with 20 mA
Pr2
Digital input polarity
Pr2
Digital input configuration
Pr2
Outputs status when open door
Pr2
Outputs restarting after doA alarm
Pr2
Digital input alarm delay
Light
relay
configuration
Pr2
terminals 3-4, XH260V terminals. 11-12):
Pr2
Serial address
Pr2
Parameter table
Pr2
Software release
Pr2
Probes display
Pr1
Access to the protected parameter list
Range
LS ÷ uS ( nu = temperature
regulation disabled )
LSH ÷ uSH ( nu = humidity
regulation disabled)
0.1°C o 1°F ÷ 25°C o 77°F
0.5 ÷ 50
-50.0°C o –58°F ÷ Set T
Set T ÷ 110°C o 230°F
0 ÷ 250 min
0 ÷ 30 min
db = dehumidifier relay.; cHu
= dehum+ compr.; c-H=
without dehum. relay
Lci ÷ Set H
Set H ÷ uci
°C ÷°F
in = integer / dE = decimal
in = integer / Hd = half digit
rE, rT, in
In, Sd
-30 ÷ +30°C / -22÷+86°F
-50,0÷110°C/ -58÷230°F
1 ÷ 120 h
0 ÷ 250 min
rt / it / SEt / dEF / dEG
0 ÷ 250 min
0÷60 min.
n ÷ y
no; yES
c-n / c-Y / o-n / o-Y
rE = relative / Ab = absolute
0°C ÷ 50.0°C / -50.0°C ÷ ALu
0°C ÷ 50.0°C / ALL ÷ 110°C
0.1°C o 1°F ÷ 25°C o 77°F
0 ÷ 250 min
0.0 ÷ 23.5 h
0 ÷ 250 min
0 ÷ 250 min
rE = relative / Ab = absolute
0 ÷ 50 / Lci ÷ AHu
0 ÷ 50 / AHL ÷ uci
0.5 ÷ 25
0 ÷ 250 min
0.0 ÷ 23.5 h
0 ÷ 250 min
0÷15
0 ÷ 250 min ( 250 = nu )
-12.0 ÷ 12.0
-12.0 ÷ 12.0
-10 ÷ 10
no = absent / YES = present
no = absent / YES = present
-999 ÷ 999
-999 ÷ 999
cL =open / oP = close
dor / PAL / EAL / bAL / Ht
on / Fan / oFF
no = no / YES = yes
0÷255 min.
ALr = alarm; dEH =
(XH260L
dehumidifier; onF = on/off; Lig
= light, ESt, dEF not select
0÷247 num
- - -
- - -
Pb1÷Pb3
- - -
4/4