Installation and Operating Instructions
XH10P - XH15P
Relative Humidity probe with 4÷20mA or 0÷10V Output (30÷90%)
XH20P - XH25P
Relative Humidity probe with 4÷20mA or 0÷10V Output (0ì÷99%)
and NTC temperature probe
1. GENERAL WARNINGS.
1.1
THE FOLLOWING SPECIFICATIONS MUST BE READ BEFORE
PROCEEDING FURTHER IN THE USE OF THE MANUAL.
• This manual is part of the product and shall be kept near the probe for easy and quick
reference.
• Check the application limits before proceeding.

1.2 SAFETY PRECAUTIONS

• The probe shall be installed by qualified personnel. In any case when the box is opened or
when the probe is going to be connected to the instrument, standard protection measures, to
avoid electrostatic discharge, have to be taken.
• Check the supply voltage is correct before connecting the probe.
• Warning: disconnect all electrical connections before any kind of maintenance.
• Make sure that the wires for probes and power wires are separated and far enough from each
other.
• In case of failure or faulty operation send the probe back to the retailer with a detailed
description of the fault.
• Dixell Srl reserves the right to change the composition of its products, even without notice,
ensuring the same and unchanged functionality.
GENERAL DESCRIPTION
2.
The XH10P and XH20P humidity probe are suitable for all those applications
where it is necessary to detect and control humidity. Such applications are:
refrigeration, drying processes, air conditioning, and others.
According to the model the probe supplies a standard output: current or voltage
signal (4÷20mA or 0÷10V) that covers a range of 0÷99% relative humidity for
XH20P and 30÷90% for XH10P.
The XH15P has the same feature of the XH10P and it's moreover provided with
NTC temperature output.
The XH25P has the same feature of the XH20P and it's moreover provided with
NTC temperature output.
The high precision and the quick reply time to external changes make these
probes extremely effective and reliable.
3. INSTALLATION
1.
Open the box of the probe. Unscrew the screws on the lid and connect the
cable to the terminals according to the model as shown at point
IMPORTANT NOTE: Internal components can be damaged by electrostatic
discharge
2.
By means of the proper holes, fix the probe where it has to measure the
humidity
.
IMPORTANT NOTE: To avoid having problem with condensing place the probe
with filter in a horizontal position or turn down.
C
B
5 5 5 5
4 4 4 4
3 3 3 3
Current output: 4÷20 mA
Only for
Supply 9÷18 Vdc: 1( ) - 2 ( )
XH15P
Supply 19÷28 Vdc: 1( ) - 3 ( )
XH25P
3.
Close the lid as shown in fig. 1, making sure that the isolation gasket is in
good condition and safely positioned in its groove.- This will guarantee a
waterproof housing.
4.
Disconnect the power supply from the instrument to which the humidity probe
is to be connected and then carry out the connection.
.
B
Ø 3÷6mm
A
2 2 2 2
1 1 1 1
3 3 3 3
2 2 2 2
1 1 1 1
+
Voltage output: 0÷10 V [2-3]
+
Supply: 12÷24 Vac / 15÷35 Vdc [1-2]
Fig. 1
rel 1.0 - 18/07/2016 - Cod.1592004100

4. DIMENSIONS

The dimensions of the humidity probe are the following:
6
48
Ø4 MAX
6
27,3
31
34
5. MAINTENANCE AND CLEANING
The probe does not require particular maintenance.- However, if it is installed in
particularly dusty places, the protective filter could become filled with dust, and as a
consequence it would alter the humidity read.- In this case it is necessary to clean
or change the filter as follows:
1.
Disconnect the instrument from the power supply
2.
Keep
on which the filter is screwed, blocked.- Now unscrew the filter by
turning it anticlockwise, making sure the sensor is not extracted.
IMPORTANT NOTE: Once the protective filter has been removed, DO NOT touch
the sensor, as it is sensitive to electrostatic charge.
3.
Change or clean the protective filter (e.g. with compressed air from the inside
towards the outside).
4.
Screw it on again carefully.
5.
Reconnect the instrument to the power supply.
6. TECHNICAL DATA
Power supply: according to the model: 19÷28Vdc or 9-20Vdc or 15÷35Vdc
Power consumption: 20mA max
Connection: 2 not polarised wires
Max cross wires: 2,5mm
2
Output: 4÷20mA or 0÷10Vdc
Measurement range: XH10P, XH15P: 30÷90% R. H.
XH20P, XH25P: 0÷99% R. H.
Protection: IP65
Operating range: XH10P, XH15P: 0÷60 °C
XH20P, XH25P: 0÷70 °C
Storage range: -30÷85 °C
RH response time: 15 sec in slowly moving air at 25°C
Accuracy at 25°C: better than 3% F. S.
DIXELL
Z.I. Via dell'Industria, 27 - 32010 Alpago (BL) ITALY - tel. +39-0437-98 33 - fax +39
- 0437 - 98 93 13 - http://www.dixell.com - e-mail: dixell@dixell.com