5.5

Motor connection

To comply with the EMC regulations, Lenze recommends to use shielded motor
ƒ
cables.
Shield clamps are not included in the scope of supply.
ƒ
(
Stop!
The user is responsible for sufficient strain relief!
Parallel connection of master and slave (motor side)
In order to connect the motor cables of master and slave to the motor, the outputs must
be connected in parallel.
It is important for the parallel connection of the inverter outputs that the outputs are
decoupled by means of an inductance between master and slave. The length of the motor
cables determine whether the inductance of the cables is sufficient for a decoupling.
2 motor connections ensure sufficient decoupling.
Decoupling via motor chokes
ƒ
If the single motor cable length is £ 10 m, master and slave must be connected in parallel
via chokes on the motor side to achieve a sufficient decoupling between master and
slave.
Decoupling via motor cables
ƒ
If the single motor cable length is > 10 m, the motor cables of master and slave can be
connected in parallel at the motor to achieve a sufficient decoupling between master
and slave.
Decoupling via motor chokes
PE
U
PE
M
PE
3~
Fig. 5−11
EDKVF9383 DE/EN/FR 4.0
V
W
PE
U
V
W
Z1
Z2
PE
Variants for parallel connection of master and slave (motor side)
Z1, Z2 Motor choke
ELM3−0003H275
ELM3−0002H320
ELM3−0002H410
l
Electrical installation
Motor connection
Decoupling via motor cables
PE U
V W
PE
PE
PE
9300VEC026
for controller
EVF9381
EVF9382
EVF9383
Fan connection
PE U
V W
PE
M
3~
9300VEC008
5
91