Lenze 9300 vector Instructions De Montage page 92

Masquer les pouces Voir aussi pour 9300 vector:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5
Electrical installation
Motor connection
Fan connection
Motor connection
BR1
BR2
40 mm
2
M6
15-20 Nm
PE
133-176 lb-in
Fig. 5−12
Cable cross−sections for the motor connection
Type
EVF9381−EV
EVF9381−EVxxxx
EVF9382−EV
EVF9382−EVxxxx
EVF9383−EV
EVF9383−EVxxxx
92
0
U
V
W
PE
max.
300 mm
3
M8
25-30 Nm
U, V, W
221-264 lb-in
Motor connection example
BR1, BR2
Brake resistor can only be operated with the variants V060, V110, V270 and V300
For connection see System Manual of 9300 vector
0
Master terminals
1
Slave terminals
2
Connect the motor cable shield with a surface as large as possible to the control
cabinet mounting plate by using the clamps.
3
Conductive surface
Ensure to have the poles right!
Do not exceed the maximum motor cable length!
Master
150
2 × 50
150
2 × 50
240
2 × 95
1)
Multiple conductor; both conductors must have the same cross−section
Observe the national and regional legislation
l
1
U
V
BR1
BR2
PE
40 mm
2
M8
25-30 Nm
U, V, W
M6
221-264 lb-in
15-20 Nm
PE
133-176 lb-in
Installation to EN 60204−1
2
U, V, W [mm
]
Slave
Master
150
1)
1)
2 × 50
150
1)
1)
2 × 50
240
1)
1)
2 × 95
W
max.
300 mm
3
9300VEC036
2
PE [mm
]
Slave
95
95
95
95
150
150
EDKVF9383 DE/EN/FR 4.0

Publicité

Table des Matières
loading

Table des Matières