Electrical installation
Control terminals
Important notes
How to connect the shield
0
1
Fig. 5−15
Terminal data
(
Stop!
ƒ
ƒ
ƒ
Cable type
Rigid
Flexible
Flexible
Flexible
96
Connection of the cable shield with shield clip and strain relief with cable binder
0
Shield sheet
1
Fasten shield sheet with two screws M4 × 12 mm at the bottom of the control card
2
Connect cable shield with shield clip to the shield sheet
3
Provide a strain relief of the control cable at the shield sheet by means of a cable binder
Connect or disconnect the terminal strips only if the controller is
disconnected from the mains!
Wire the terminal strips before connecting them!
Unused terminal strips must also be plugged on to protect the contacts.
Wire end ferrule
Without wire end
ferrule
Wire end ferrule
without plastic sleeve
Wire end ferrule with
plastic sleeve
l
2
3
Maximum cable
Tightening torque Stripping
cross−section
2
2.5 mm
(AWG 14)
2
2.5 mm
(AWG 14)
2
2.5 mm
(AWG 14)
2
2.5 mm
(AWG 14)
9300vec063
length
0.5 ... 0.6 Nm
5 mm
(4.4 ... 5.3 lb−in)
EDKVF9383 DE/EN/FR 4.0