5.4.4 New battery

The page NEW BATT is used in case battery circuit breaker BCB is not closed, when
requested, in the start-up phase. In this case the system will start considering the battery
completely discharged and activating the alarm "A10 – BATTERY FAULT".
To set the battery autonomy to 100% it is necessary to access the section and confirm the
operation in the confirmation page.
In case of distributed battery configuration such section is disabled and can be found in the
Settings section of each power module.

5.4.5 Setting the RS485 user interface parameters

The parameters regarding the communication via RS485 interface can be set in the MODBUS
RS485 section.
This section allows to set the ModBus address, the communication mode and the data
transmission speed.

5.4.6 Setting the display network parameters

The NETWORK CONFIG section allows to configure the parameters related to the LAN network
and to the system time synchronization server.
All the parameters that can be set in this section are related to the communication port (LAN)
available on-board the touch screen.
Picture 26 – Touch screen network parameters setting

5.4.6.1 Setting the LAN parameters

The LAN network parameters which can be set are the following:
 IP address
 Network mask
 Network gateway
 Primary DNS server
 Secondary DNS server
 DHCP Enabling / Disabling
UPS user manual
Manuel de l'utilisateur de l'ASI
Utilizzo dell'UPS
OMP06263 REV. B