Installation and start-up of KEOR HPE UPS 400-500 kVA
Installation et démarrage de l'ASI KEOR HPE 400-500 kVA
Installazione e avviamento KEOR HPE UPS 400-500 kVA
Phase conductor cross sect. [mm
Neutral conductor sizing
Earth conductor cross sect. [mm
Conductor max. cross section [mm
Max. number of conductors
Fixing bolt dimensions
Tightening torque [Nm]
The sections given in the table above are indicative only. The cables have been designed according
to the standard CEI-UNEL35024/1, using the following data:
 70° C rated PVC copper cables
 ambient temperature equal to 40° C
 maximum length of the cables equal to 30 m (voltage drop < 0,5%)
 cables laid in cavities of structures or solid bottom cable trays
The given cross sections do not take into account the overload currents allowed by each line, which
are detailed in the product Technical Specification.
The UPS manufacturer is not responsible for the correct sizing of the device supply and output lines
for which the plant conditions and operating temperatures, which are specific of each electrical
installation, must be taken into account.
Rectifier input [A]
Bypass input / Output [A]
Battery [A]
(1)
Values referred to 400Vac rated voltage
(2)
For the overload values refer to the Technical Specification
Details of the electrical connections
Power (kVA)
Input fuses [A]
Rectifier
Bypass
Rectifier
Bypass
Output
Battery
Linear load
NON-linear load
Power connections
Type
Rated current (at full load and battery recharging)
Power (kVA)
(1)
(1) (2)
400
800
630
2
]
4x (2x240)
4x (2x185)
4x (2x185)
3x (2x240)
Same as the phase conductor
1,5 x phase conductor cross section
2
]
240
2
]
240
2
400
676
578
658
500
1000
800
4x (3x240)
4x (2x300)
4x (2x300)
3x (2x300)
2x185
Aluminium bars
300
M12
69 ÷ 85
500
756
722
822
OMT87187 REV. A
3
31