LEGRAND KEOR HPE Manuel De Fonctionnement page 208

400-500 kva
Masquer les pouces Voir aussi pour KEOR HPE:

Publicité

Les langues disponibles

Les langues disponibles

Status
S8
Description
The inverter is synchronized with the MASTER UPS.
Operating
This status is only present on the SLAVE UPS units, and shows that the
condition
inverter is synchronized with the signal sent by the MASTER UPS.
Status
S14
Description
The battery is charging.
Operating
The battery static switch is closed and the battery is in the first phase of
condition
the I/U charging mode (DIN 41773), with constant current and
increasing voltage.
Status
S15
Description
The battery is charging.
Operating
The battery static switch is closed and the battery is in the second and
condition
final phase of the I/U charging mode (DIN 41773), with constant voltage
and decreasing current.
Status
S16
Description
Switching with high bypass voltage
Operating
Switching from inverter to bypass with inverter switch-off caused by the
condition
bypass voltage greater than or equal to 10% of the rated voltage.
Status
S23
Description
Fault UPS clock.
Operating
The UPS clock is not working properly.
condition
Status
S24
Description
UPS operating status.
Operating
The UPS is in the GREEN CONVERSION operating state.
condition
Status
S25
Description
The UPS is starting.
Operating
The UPS is in a phase of the startup sequence.
condition
Manuel de l'utilisateur de l'ASI
INVERTER MASTER SYNCHRONIZED
BATTERY CHARGE I
BATTERY CHARGE U
HIGH BYPASS COMMUTATION
RTC ERROR
GREEN CONVERSION
STARTUP SEQUENCE
UPS user manual