LEGRAND KEOR HPE Manuel De Fonctionnement page 73

400-500 kva
Masquer les pouces Voir aussi pour KEOR HPE:

Publicité

Les langues disponibles

Les langues disponibles

Picture 19 – Bypass start-up
3)
Close the battery switch BCB when indicated by the display.
Picture 20 – Connecting the battery
4)
Close the output switch OCB when required and immediately after the display will require to
open the manual bypass switch MBCB. The inverter will start.
Picture 21 – Closing the UPS output switch
48
OMT87187 REV. A
Installation and start-up of KEOR HPE UPS 400-500 kVA
Installation et démarrage de l'ASI KEOR HPE 400-500 kVA
Installazione e avviamento KEOR HPE UPS 400-500 kVA