LEGRAND KEOR HPE Manuel De Fonctionnement page 218

400-500 kva
Masquer les pouces Voir aussi pour KEOR HPE:

Publicité

Les langues disponibles

Les langues disponibles

Alarm
A40
Description
UPS stopped due to the operation of the protection sensor as a result of
high sudden DC voltage variations under the limits.
Possible
 DC bus voltage problem.
causes
Solutions
1. Check that there aren't short circuit in DC bus.
2. Verify the status of the UPS.
3. Verify the battery blocks.
4. Verify the DC voltage value.
5. If the alarm persists, contact our Technical Support Service.
Alarm
A41
Description
The DC current is over the limits.
Possible
 The UPS detected the DC current out of limits and switch off the
causes
Solutions
1. Check that there aren't short circuit in DC bus.
2. Check the battery current sensor.
3. Check the battery blocks.
4. If the alarm persists, contact our Technical Support Service.
Alarm
A42
Description
Failure of the redundant auxiliary power supply.
Possible
 Internal fault.
causes
Solutions
1. Contact our Technical Support Service.
Alarm
A43
Description
UPS output current sensor has detected the peak current.
Possible
 Load problem.
causes
 Measuring circuit failure.
Solutions
1. Check the peak of the output current.
2. Check the output current sensor.
3. If the alarm persists, contact our Technical Support Service.
Manuel de l'utilisateur de l'ASI
MIN DC VOLTAGE
MAX DC BATTERY CURRENT
inverter, booster and disconnected the battery from the UPS.
LOST OF REDUND POWER SUPPLY
MAX LOAD CURRENT
UPS user manual
Utilizzo dell'UPS
OMP06263 REV. B
59