Alarm
A50
Description
The inverter current sensor has detected a peak of the current and the
control inverter is in limitation.
Possible
Load problem.
causes
Measuring circuit failure.
Solutions
1. Check the loads connected to the UPS output.
2. If the alarm persists, contact our Technical Support Service.
Alarm
A51
Description
The battery temperature is out of tolerance. This alarm is only active
when the temperature probe is installed and enabled on the battery.
Possible
Anomalous temperature in the battery cabinet.
causes
Possible failure on the measuring circuit.
Solutions
1. Check the temperature on the batteries and remove the cause of
the alarm, if any.
2. If the alarm persists, contact our Technical Support Service.
3.
Alarm
A52
The inverter is blocked because of an anomaly on the control power
Description
supply.
Possible
Internal error.
causes
Solutions
1. Contact our Technical Support Service.
Alarm
A53
Description
The controller has detected an incompatibility in the control software.
Possible
The software update was not performed properly.
causes
Solutions
1. Contact our Technical Support Service.
Alarm
A54
Description
Internal error.
Possible
Microcontroller communication problems.
causes
Solutions
1. Contact our Technical Support Service.