Parameter settings
Parameters
Setting range
Min / Max
Water pres-
0.1 – 5.0 bar
sure, max.
Water pres-
0.1 – 5.0 bar
sure, target
Maximum
0.1 – 5.0 bar
pressure loss
Tab. 7-13 Parameter in the "Sensors" menu
7.6.2

Menu: Heating circuit config.

[→ Main menu → Configuration → HC config]
Parameters
Setting range
Min / Max
Weather-com-
pensated
Feed temperat-
ure, fixed
Weather-com-
pensated
Frost protec-
Off
tion temperat-
-15 – 5 °C
ure
Building insu-
Off
lation
low
Normal
Good
Very good
Switch temp.
heating circuit
Off
10 – 40 °C
Tab. 7-14 Parameter in the "Heating circuit config." menu
7.6.3

Menu: Heating

[→ Main menu → Configuration → Heating]
Parameters
Setting range
Min / Max
Heat limit,
Off
heating mode
10 – 40 °C
Heat limit, re-
Off
ducing mode
10 – 40 °C
Heating curve
0.0 – 3.0
Operating Instructions
38
Description
Defines the maximum water pressure.
Pressure monitoring function (only with activated pressure sensor, [Water
pressure sensor] = On): If the measured value exceeds the set value, a
warning message is generated.
Defines the target water pressure.
Pressure monitoring function (only with activated pressure sensor, [Water
pressure sensor] = On): If the measured value falls below the set value by
more than the value set in the [Maximum pressure loss] parameter, a
warning message is generated.
Defines the maximum acceptable pressure loss in the heating system.
Pressure monitoring function (only with activated pressure sensor, [Water
pressure sensor] = On): If the measured value falls below the set value by
more than the value set in the [Water pressure, target] parameter, a warn-
ing message is generated.
Description
Selection of the method for determining the target feed temperature.
Feed temperature, fixed: Control to a fixed flow value (depending on oper-
ating mode)
Weather-compensated: Weather-compensated control based on the heat-
ing curve
No frost protection of the HC
If the outside temperature drops below the set value, the system switches
to frost protection operation (the pumps are switched on). The function is
ended if the outside temperature rises above the set value +1 K.
Setting the building insulation standard. This influences the averaged out-
side temperature and the automatic adaptations of the heating curve and
the heating times.
Automatic activation of cooling mode.
Deactivated
If the outside temperature exceeds the set value, the system is switched to
the "Cooling" operating mode. If the outside temperature falls 2 K below
the set value, the system automatically switches back to the previously ac-
tivated operating mode
Description
Setting of the automatic summer switch-off of the heating operation. If the
outside temperature measured and averaged by the controller exceeds the
set value by 1 K, the HC is switched off. The heating is released again if
the outside temperature undercuts the set heating limit.
Setting the heating limit for the "switch-off" of the heating circuit during the
setback time (functioning as in [Heat limit, heating mode] parameter).
Only if [Weather-compensated] parameter = Weather-compensated:
Setting of the heating curve. The heating curve reflects the dependence of
the target feed temperature of the HC on the outside temperature (see
Chap.
4.5).
Factory
Incre-
Access
setting
ment
BE HF
3.0 bar
0.1 bar
N
E
0.9 bar
0.1 bar
N
E
0.5 bar
0.1 bar
N
E
Factory
Incre-
Access
setting
ment
BE HF
-
N
E
0 °C
1 °C
E
E
-
E
E
1 °C
N
E
Factory
Incre-
Access
setting
ment
BE HF
19 °C
1 K
E
E
10 °C
1 K
E
E
0.5
0.1
E
E
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN