Configuration; Menu: Sensors - Daikin RoCon+ HP1 ETSH16P30D Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 117
Parameters
Setting range
Min / Max
Heating sup-
3 – 40 kW
port power
Heating sup-
2 – 15
port hysteresis
Heating sup-
5 – 85 °C
port max.
temp.
Min. pump
40 – 80%
power
Max. pump
60 – 80%
power
Tab. 7-12 Parameter in the "Intelligent Storage Mgmt" menu
7.6

Configuration

[→ Main menu → Configuration]
7.6.1

Menu: Sensors

[→ Main menu → Configuration → Sensors]
Parameters
Setting range
Min / Max
Outside tem-
Integrated
perature
sensor
sensor (*)
Optional sensor
Hot water
sensor
Inactive
Sensor
Thermostat
Water pres-
sure sensor
Off
On
Outside tem-
-5.0 – +5.0 K
perature cor-
rection
Water pres-
0.1 – 5.0 bar
sure, min.
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Description
The setting limits the heating support output.
Only if [Heating support (HZU)] parameter = On.
Heating support is activated if
Tdhw > THZUmin + 4 K and Tdhw > [Feed temperature, target] + 1 K.
Heating support is deactivated if
Tdhw < THZUmin or Tdhw < [Feed temperature, target].
THZUmin = currently active hot water target temperature [Feed temperat-
ure, target] + set [Heating support hysteresis] parameter value.
Tdhw = current hot water storage tank temperature
[Feed temperature, target] = currently active feed target temperature (see
Chap.
4.5)
The setting limits the target feed temperature (measured against t
when the heating support function is active.
Lower limit for pump operation. Only used when heating support is active
or heat is generated by an external heat source. During normal operation,
the pump is controlled according to the [Pump limit] parameter, see
Chap.
7.5.2.
Upper limit for pump operation. Only used when heating support is active
or heat is generated by an external heat source. During normal operation,
the pump is controlled according to the [Pump limit] parameter, see
Chap.
7.5.2.
Description
Selection of whether the sensor integrated in the outdoor unit or an op-
tional outside temperature sensor is used to determine the target feed tem-
peratures
Configuration of the domestic hot water preparation:
No function for domestic hot water preparation.
Function for domestic hot water preparation is activated. A storage temper-
ature sensor is evaluated for domestic hot water preparation (if no storage
temperature sensor is connected, an error message is generated).
Function for domestic hot water preparation is activated. A thermostatic
switch (ON/OFF) is evaluated for domestic hot water preparation where an
"open terminal" is evaluated as "not required".
Configuration of the sensor for detecting the water pressure of the system.
No sensor evaluation
Sensor evaluation activated (if no pressure sensor is connected, an error
message is generated.)
Individual adjustment for the measured value of the outside temperature
relevant for the controller.
Defines the minimum water pressure.
Pressure monitor function (only with activated pressure sensor, [Water
pressure sensor]= On): If the measured value falls below the set value, the
Daikin Altherma ETS(X/H) is switched off and an error message gener-
ated.
7
Parameter settings
Factory
Incre-
setting
ment
15 kW
1 kW
5
1
)
60 °C
1 °C
V, BH
50%
1%
80%
1%
Factory
Incre-
setting
ment
-
-
-
0.0 K
0.1 K
0.5 bar
0.1 bar
Operating Instructions
Access
BE HF
N
E
N
E
N
E
N
E
N
E
Access
BE HF
N
E
N
E
N
E
N
E
N
E
37