Parameter settings
7.3

User

[→ Main menu → User]
7.3.1

Menu: Room temperature target

[→ Main menu → User → Room]
Parameters
Setting range
Min / Max
Room temper-
5 – 40 °C
ature target 1
Room temper-
5 – 40 °C
ature target 2
Room temper-
5 – 40 °C
ature target 3
Tab. 7-2
Parameter in the "Room temperature target" menu
7.3.2

Menu: Reduce room temperature

[→ Main menu → User → Reduce]
Parameters
Setting range
Min / Max
Reduce room
5 – 40 °C
temperature
Tab. 7-3
Parameter in the "Reduce room temperature" menu
7.3.3

Menu: Room temperature absent

[→ Main menu → User → Absent]
Parameters
Setting range
Min / Max
Room temper-
5 – 40 °C
ature absent
Tab. 7-4
Parameter in the "Room temperature absent" menu
7.3.4

Menu: Hot water temperature, target

[→ Main menu → User → Hot water]
Parameters
Setting range
Min / Max
Hot water tem-
35 – 70 °C
perature target
1
Hot water tem-
35 – 70 °C
perature target
2
Hot water tem-
35 – 70 °C
perature target
3
Tab. 7-5
Parameter in the "Hot water temperature, target" menu
7.3.5

Menu: 1 x hot water

[→ Main menu → User → 1x load]
Parameters
Setting range
Min / Max
1 x hot water
Off
On
Tab. 7-6
Parameter in the "1 x hot water" menu
Operating Instructions
30
Description
Target value of the room temperature in °C, which is valid for the 1st
switching time cycle of the [Automatic 1] and [Automatic 2] time programs.
Target value of the room temperature in °C, which is valid for the 2nd
switching time cycle of the [Automatic 1] and [Automatic 2] time programs.
Target value of the room temperature in °C, which is valid for the 3rd
switching time cycle of the [Automatic 1] and [Automatic 2] time programs.
Description
Target value of the reduced room temperature in °C, which is valid for the
[Automatic 1] and [Automatic 2] time programs.
Description
Target value of the reduced room temperature in °C, which is valid for the
[Absent] + [Holiday] time programs.
Description
Target value of the hot water temperature in °C, which is valid for the 1st
switching time cycle of the [Automatic 1] and [Automatic 2] time programs.
Target value of the hot water temperature in °C, which is valid for the 2nd
switching time cycle of the [Automatic 1] and [Automatic 2] time programs.
Target value of the hot water temperature in °C, which is valid for the 3rd
switching time cycle of the [Automatic 1] and [Automatic 2] time programs.
Description
Start of one-time domestic hot water preparation to the set target value
[Hot water temperature target 1] without time limit, independent of the heat-
ing programs.
Factory
Incre-
Access
setting
ment
BE HF
20 °C
0.5 °C
E
E
20 °C
0.5 °C
E
E
20 °C
0.5 °C
E
E
Factory
Incre-
Access
setting
ment
BE HF
15 °C
0.5 °C
E
E
Factory
Incre-
Access
setting
ment
BE HF
15 °C
0.5 °C
E
E
Factory
Incre-
Access
setting
ment
BE HF
48 °C
0.5 °C
E
E
48 °C
0.5 °C
E
E
48 °C
0.5 °C
E
E
Factory
Incre-
Access
setting
ment
BE HF
-
E
E
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN