Parameters
Setting range
Min / Max
Room thermo-
stat
No
Yes
Interlink func-
tion
Off
On
Programmable
output (230 V)
Inactive
Heating circuit
request
Circulation re-
quest
Direct heating
circuit request
Func. burner
Resistance val-
blocking con-
ues
tact
Burner blocking
contact
Daikin RoCon+ HP
Daikin controller RoCon+ HP1
008.1447899_00 – 09/2019 – EN
Description
Configuration of a room thermostat with potential-free contacts connected
to Daikin Altherma ETS(X/H) connection J16.
Deactivated
Only if [Interlink function] parameter = Off:
Evaluation of the heating and cooling switching contacts at plug connection
J16 on the RoCon BM2C PCB (only if none of the "Standby", "Reduce",
"Summer", "Holiday", "Public holiday" or "Screed" is active):
▪ Closed heating switching contact: Operating mode is switched to "Heat-
ing". Priority if both switching contacts are closed.
▪ Closed cooling switching contact: Operating mode is switched to "Cool-
ing".
Open contacts: Only frost protection active.
Configuration for systems that are operated with 2 different feed target
temperatures (see
Chap.
4.4.4).
One possible application is, for example, the additional integration of an
HP convector in a surface heating and cooling system.
Prerequisite: 2 room thermostats are connected to Daikin Altherma ETS(X/
H) plug connection J16.
Deactivated
Evaluation of the heating nd cooling switching contacts at plug connection
J16 on the RoCon BM2C PCB.
Activation of cooling mode only by switching the operating mode to "Cool-
ing" (see
Chap.
4.1).
Setting of the [Room thermostat] parameter is no longer evaluated.
▪ Open switching contacts: Only frost protection active
▪ "Heating" and "Automatic 1" / "Automatic 2" operating mode active dur-
ing the switching cycles in day mode.
▪ Closed heating switching contact = IL1:
▪ It is regulated to the normal feed target temperature in accordance
with the parameter settings in [→ Main menu → Configuration
→ Heating].
▪ Closed cooling switching contact = IL2:
▪ The system is regulated to the increased feed target temperature (nor-
mal feed target temperature + value of the [Interlink temperature in-
crease ] parameter. Priority if both switching contacts are closed!
▪ "Cooling" operating mode active.
▪ Closed heating switching contact = IL1:
▪ It is regulated to the normal feed target temperature in accordance
with the parameter settings in [→ Main menu → Configuration
→ Heating].
▪ Closed cooling switching contact = IL2:
The system is regulated to the reduced feed target temperature (normal
feed target temperature value of the [Interlink temperature reduction] para-
meter. Priority if both switching contacts are closed
Configuration of the multi-function output (230 V, J14 connection):
The output has no function.
Header pump – The output becomes active as soon as any heating circuit
(e.g. mixer circuit) of the system reports a heat request to the heat gener-
ator.
Circulation pump – The output is activated either after the time program of
the circulation pump or after the time program of the domestic hot water
preparation, depending on the parametrisation (see
Feeder pump – The output becomes active as soon as a heat requirement
is pending for the direct heating circuit of the heat generator.
Selection of the functionality of the EXT switching contact (J8) (see
Chap.
4.1)
7
Parameter settings
Factory
setting
Chap.
4.3).
Incre-
Access
ment
BE
HF
-
N
E
-
N
E
-
N
E
-
N
E
Operating Instructions